Axial flow fans play key roles in the thermo-flow performance of direct dry cooling system under windy conditions, so the energy efficiency of a power generating unit can be improved by optimizing the operation strategies of the axial flow fans. In this work, various measures based on the partition adjustment of axial flow fans with constant power consumption of a 2 × 660 MW power plant are studied by computational fluid dynamics (CFD) methods. The results show that increasing the rotational speed of the windward fans is beneficial to reduce the inlet air temperature and increase the mass flow rates of the fans, which enhance the heat rejections of the air-cooled condensers, especially at high wind speeds. Moreover, the turbine back pressures for the optimal and original cases are achieved by iterative methods, with the largest drop of 2.77 kPa at the wind speed of 12 m/s for 110-case 3 in the wind direction of −90°. It is recommended to adopt 110-case 1 and 110-case 3 at low and high wind speeds, respectively, in the wind directions of 90° and −90°, while 110-case 2 is always the best choice in the 0° wind direction.
The operating conditions of axial flow fans are closely related to the thermo-flow characteristics of the mechanical draft direct dry cooling system. Moreover, the uneven distribution of cooling air driven by axial flow fans may lead to the deterioration of the heat transfer capacity of air-cooled condensers (ACCs). Therefore, developing energy-saving operating methods for axial flow fans is very meaningful. In this work, two kinds of adjustment strategies to make the flow field more uniform are proposed for a 2 × 300 MW direct dry cooling power-generating unit. The performance of ACCs in the prevailing wind direction is predicted with the help of the macro heat exchanger model. It is found that the inlet air temperatures of fans are significantly reduced by proposed strategies, especially at high wind speeds. Moreover, the minimum cooling air can meet the cooling demand of ACCs for the strategy which made the air flow rates of all fans consistent. Compared with the case without adjustment of fans, the total power consumption of the fan array was cut down effectively, up to 13.94% at the wind speed of 12 m/s. In conclusion, the energy efficiency of ACCs can be improved by the uniform flow field.