Distributed power generation systems (DPGSs) based on inverters require reliable islanding detection algorithms (passive or active) in order to determine the electrical grid status and operate the grid-connected inverter properly. These methods are based on the analysis of the DPGS voltage, current, and power in time or frequency domain. This paper proposes a time-frequency detection algorithm based on monitoring the DPGS output power considering the influence of the pulsewidth modulation, the output LCL filter, and the employed current controller. Wavelet analysis is applied to obtain time localization of the islanding condition. Simulation and experimental results show the performance of the proposed detection algorithm in comparison with existing methods.
This paper offers an overview of the passive methods used for islanding detection. A monitoring PLL has been adopted for the estimation of the voltage amplitude and frequency. Passive inverter resident methods discussed are the over/under voltage (OUV), over/under frequency (OUF), the voltage harmonic monitoring (with a study on the effects of the grid impedance value and of the inverter DC voltage ripple) and the phase monitoring (different from the classical phase jump method). A harmonic synchronization PLL is used to monitor the 3 rd , 5 th and 7 th harmonics. All the proposed algorithms are validated by simulations and experimental results obtained in accordance with the IEEE Std. 929-2000 procedure
1 October 2006 in IEEE Transactions on Industrial Electronics
The detection of the islanding condition of a distributed generation (DG) system is crucial for safety reasons, as discussed in the IEEE standards and specifically required by some national codes. Several anti-islanding methods that are resident in the inverter have been investigated and classified as passive (measurement of the natural effects of islanding) or active (based on the measurement of the effects due to transients or harmonics deliberately introduced in the system). In case the power drained by the load matches the power generated by the DG inverter, the effect of islanding is small, and the passive methods fail. However, the active methods, which have been developed to overcome these limits, create disturbances that can interact with those generated by other DG systems. In this paper, a new anti-islanding method is proposed. It exploits the natural sensitivity of a grid-voltage sensorless control to disturbances to highlight the islanding condition. The adopted grid-voltage sensorless control is adapted to a single-phase system with the use of resonant controllers based on the internal model control law: resonant-controller-based observer results. Then, a Kalman-filter-based algorithm is used to detect the islanding condition based on the energy mismatch between the estimated third and fifth harmonics and the real ones. Experimental results support the analysis
9 July 2007 in IEEE Transactions on Power Electronics
The monitoring and rejection of voltage and current harmonics in power electronics applications such as power quality conditioners or distributed generation systems require correct estimation algorithms especially if the harmonic amplitudes are time varying. Power signal decomposition in multiple synchronous rotating reference frames (MSRFs) is considered one of the best solutions. The most commonly employed implementations of this signal transformation are based on phase-locked loops (PLLs), recursive discrete Fourier transforms (RDFT), or discrete Kalman filtering (DKF). In this paper, a rigorous analysis of the performance of these implementations has been carried out. Complete tests have been performed to evaluate the computational burden, the frequency domain response, and the tolerance to low frequency amplitude variations. The results make it possible to select the proper method depending on the requirements of each application.
1 March 2010 in IEEE Transactions on Industrial Electronics
Grid-connected photovoltaic (PV) inverters employ an islanding-detection functionality in order to determine the status of the electrical grid. In fact, the inverter must be stopped once the islanding operating mode is detected according to standards and grid-code limits. Diverse islanding-detection algorithms have been proposed in literature to cope with this safety requirement. Among them, active methods based on the deliberate perturbation of the inverter behavior can minimize the so-called nondetection zone, which is a range of conditions in which the inverter does not recognize that it is operating in an undesired island. In most cases, the performances of these methods have been analyzed considering a highly dispersed generation scheme, where only one distributed-generation power system is connected to the local electrical power system (EPS). However, in some studies, it has been highlighted that if two or more PV inverters are connected to the same local EPS, their anti-islanding algorithms do not behave ideally and can fail in detecting the islanding condition. However, there is no systematic study that has investigated the overall capability of different anti-islanding methods employed on several inverters connected to the same EPS to detect islanding condition. This paper is a first attempt to carry out a systematic study of the performances of the most common active detection methods in a case of two inverters connected to the same EPS. In order to evaluate the global capability of the two systems to detect islanding condition, a new performance index is introduced and applied also to the case when the two inverters employ different anti-islanding algorithms.
9 March 2018 in IEEE Transactions on Industrial Electronics
The proliferation of nonlinear loads and the increasing penetration of distributed energy resources in medium-voltage (MV) and low-voltage (LV) distribution grids make it more difficult to maintain the power quality levels in residential electrical grids, especially in the case of weak grids. Most household appliances contain a conventional power factor corrector (PFC) rectifier, which maximizes the load power factor (PF) but does not contribute to the regulation of the voltage total harmonic distortion (THD V ) in residential electrical grids. This paper proposes a modification for PFC controllers by adapting the operation mode depending on the measured THD V . As a result, the PFCs operate either in a low current total harmonic distortion (THD I ) mode or in the conventional resistor emulator mode and contribute to the regulation of the THD V and the PF at the distribution feeders. To prove the concept, the modification is applied to a current sensorless nonlinear controller applied to a single-phase boost rectifier. Experimental results show its performance in a PFC front-end stage operating in the continuous conduction mode connected to the grid with different THD V .