Aiming at solving the problems of substantial error in the existing methods due to mutual reactance in locating the catenary-to-ground fault of a two-track railway system(TTRS), a novel fault location method considering mutual reactance is proposed. The proposed method can effectively eliminate the influence of mutual reactance on fault location. In addition, the fault location can obtain from fault reactance measured at line circuit-breaker of the traction substation. Simulation results show that the proposed method can obviously improve the accuracy of fault location.
Because of sectioned power supply, there are a series of no-electricity neutral sections in every electrified railway. The way of a train running through neutral section is a special challenge for railway. A technology for multiple unit train directly running through neutral section with electric load and an automatic system based on this technology are introduced in this paper. With the use of this technology, the neutral segment can be electric fed by the two adjacent feeder lines one after another, and the electricity supply with the train hardly interrupted. It is no more necessary for the trains to frequently shut off electric load before neutral sections like in existing electrified railways, and it is also helpful to reduce speed loss and make passengers feel more comfortable. A prototyping system has been implemented and experimentally tested.
1 May 2023 in IEEE Transactions on Transportation Electrification
In high-speed railway (HSR), directly reclosing a circuit breaker after a fault trip can result in a large second overcurrent, causing insulation degradation, equipment damage, and even system instability. Meanwhile, existing direct reclosing schemes fail to simultaneously identify the faulty line, fault property, and fault type, especially for all-parallel autotransformer traction networks (AATNs). Therefore, an adaptive reclosing scheme for AATNs based on multi-source information is proposed in this paper, including two critical methods of faulty line identification, and fault property and type identification. Specifically, a multi-source fault impedance angles integrated faulty line identification method is proposed to effectively distinguish the faulty line and healthy line. Moreover, a novel approach is developed to incorporate multi-source line-to-line induced voltages obtained by reclosing the healthy line, which facilitates the fault property and type identification. The effectiveness and superiority of the proposed reclosing scheme are demonstrated using field tests and simulation experiments. In addition, the proposed scheme not only shortens the power outage time of healthy line, but also completely avoids second damages to equipment, and prevents power outages when the feeder is permanently faulted to the ground, presenting its remarkable robustness benefiting from multi-source information.
30 June 2023 in IEEE Transactions on Power Delivery
Aiming at the problem that the existing relay protection of traction power supply system mis-operates when an out-of-phase fault occurs, based on the sum of two phase impedance, a novel distance protection method is proposed. In addition, the characteristic and settings of the proposed protection are derived in detail. Simulation results verify the effectiveness and superiority of the proposed protection method.
The existing fault location methods for all-parallel autotransformer railway systems (AARS) have limitations because they are generally designed for several given feeding conditions. In alternate feeding conditions, the existing fault location methods do not work well and may have large errors. To solve this problem, we have proposed a generalized fault location scheme for AARS in this paper. After analyzing the fault characteristics of AARS, we classified the feeding conditions of the faulted section of AARS into three types and introduced the corresponding fault location methods. In order to identify the faulted section and its feeding condition, we first formed a switch state matrix based on the adjacency matrix and mapped the fault current distribution into a current state matrix, then we unified the two matrices into a fault state matrix to reflect the fault state of the AARS. Finally, a generalized fault location scheme was proposed based on a fault state matrix. The proposed scheme effectively eliminates the negative influence of feeding conditions on the fault location, and it can identify the fault type and locate faults in different feeding conditions. Several simulation cases verified the effectiveness of the proposed scheme.