In this paper, a cascaded two-level hybrid control scheme based on multi-variable robust H ∞ and proportional integral control is proposed for primary frequency control of an island mode microgrid consisting of a diesel engine generator, a photovoltaic energy source, an energy storage system, and an aggregated static load. Topological and nonlinear averaged models of each subsystem are introduced, followed by linearized frequency-control-oriented modelling of the entire system. Then, for currents control, conventional proportional-integral-based tracking controllers placed on a lower control level are designed, with their reference values generated from the output of an H ∞-control-based upper level. A comprehensive methodology that casts the specific engineering demands of microgrid operation into the H ∞ control formalism is outlined. Additionally, it is demonstrated how closed-loop dynamic performance requirements must at their turn be taken into account in the initial microgrid setup and sizing, namely in appropriately choosing and rating the energy storage system. Numerical simulations performed with MATLAB®/Simulink® show the validity and effectiveness of the proposed frequency robust control technique in the presence of multiple photovoltaic power step changes on a kVA-rated microgrid. A robust performance analysis of the previously designed H ∞ controller is performed under numerous uncertainty levels in the steady-state value of the supercapacitor state of charge and multiple photovoltaic power step changes to determine if the closed-loop system remains robust from a performance standpoint around its nominal design. The H ∞ control design procedure allows a further investigation on how to link time-domain dynamic performance specifications (e.g., desired control objectives) and frequency-domain specifications (e.g., via so-called weighting functions) in a systematic and optimal manner (i.e., automation for their design or expert modelling), from which an useful guide can be created for practical control engineers in the future. Distinct photovoltaic penetration rate scenarios together with respective computed H ∞ controllers, on the other hand, are examined to determine whether or not an H ∞ optimal control solution that is robust in performance to a variety of photovoltaic power step variations relative to the rated operating point can always be generated.
This paper proposes a multi-variable robust control scheme for voltage regulation in a diesel-photovoltaic-supercapacitor hybrid power generation system operating in stand-alone mode. First, we study the influence of system parameters on the dynamic behavior of open-loop system measured outputs by means of a stability analysis method based on Monte Carlo simulation. Next, by applying $\mathcal {H}_{\infty }$ control theory, an $\mathcal {H}_{\infty }$ -based voltage controller is proposed to robustly force the voltage magnitude of a point of common coupling such as to satisfy design specifications. A cascaded two-level control architecture, where this controller acts as an upper control level and provides references to classical PI-based current tracking controllers placed on a lower level, is developed. A comprehensive methodology that casts the specific engineering demands of microgrid operation into an $\mathcal {H}_{\infty }$ control formalism is detailed. Effectiveness of the proposed voltage robust control strategy is validated via MATLAB ® /Simulink ® closed-loop time-domain simulations. Finally, we perform a sensitivity analysis of robust performance of the designed $\mathcal {H}_{\infty }$ controller in the presence of various load disturbances and model uncertainties through a series of closed-loop time-domain simulations carried out in MATLAB ® /Simulink ® .
In this paper, different control strategies are presented for primary frequency regulation in a diesel-photovoltaic-supercapacitor hybrid power generation system. Firstly, a classical control approach is proposed as a reference. Then, a robust control design based on H ∞ control theory is applied to the studied system. Starting from given certain desired performances, Linear Matrix Inequalities (LMI) are used to solve the H ∞ controller design problem. In the second step, several modeling uncertainties are included and μ-analysis is carried out to determine the maximum variation range of each uncertainty for which the system is still stable and desired performances are met. Numerical simulation results show the effectiveness of the H ∞ robust control strategy when compared with the classical control strategy used for this type of hybrid power generation system.