Failures in traction power supply system (TPSS) may cause high-speed trains to run behind the schedule or even suffer from downtime, which would directly affect the entire scheduling and cause inestimable loss. Therefore, it is crucial to evaluate the reliability of the TPSS to ensure that it can operate with high reliability. This paper proposes a method for evaluating the overall reliability of the TPSS as-sociated with high-speed railway (HSR) considering relay protection. The impact of relay protection on the reliability of the TPSS is analyzed, then the failure mode and effects analysis tables are established based on the main wiring dia-gram of the TPSS and its equipment composition to qualita-tively analyze the failure modes of primary and secondary equipment and their influence. According to the FMEA ta-bles, the fault tree model of the traction substation and cate-nary system considering relay protection is established re-spectively, and the system reliability indexes are calculated through Monte Carlo simulation. Different from existing studies, the reliability models established in this paper take into account the primary and secondary equipment of the TPSS and coupling relationship between them, and highlight the configuration of relay protection and its logic cooperating with each equipment. Through the analysis of practical ex-ample concerning the TPSS serving China's HSR, it shows that rich and direct system reliability indexes can be obtained through simulation with the proposed reliability models and evaluation method, and the impact of relay protection on sys-tem reliability can be reflected, which provides an effective means for evaluating the overall reliability of the TPSS.
7 May 2021 in IEEE Transactions on Transportation Electrification
Catenary is essential for electric locomotives to obtain electric energy, and it is crucial to the normal and stable operation of electric locomotives. However, the catenary is completely exposed outdoors without backup equipment. Therefore, compared with other power supply equipment in traction substation, catenary is more likely to be affected by external geographical and meteorological factors. In order to comprehensively assess the probability and consequence of catenary failures under the impact of external geographical and meteorological factors, a risk assessment method for electrified railway catenary is proposed in this article. First, the influence of external geographical and meteorological factors on catenary failures is analyzed based on the actual operation records. Then, considering the high efficiency and service characteristics of railway transportation, the risk consequence indicators are established, and the cumulative risk of catenary failure is quantitatively evaluated. Based on this, the risk classification method is proposed, and the risk level of catenary is visualized with geographic information system (GIS) technology. Finally, the risk contribution indicator is proposed to describe the influence of catenary component on the total risk of catenary failures. The catenary failure records of Beijing–Shanghai Railway within the administration of Shanghai Railway Bureau in 2017 are used for a study case. The results show that the proposed method can comprehensively quantify and visualize the risk of catenary failures. Also, the critical components of the catenary system can be identified, which can provide effective information for the maintenance decision-making process.
A traction power-supply system (TPSS) is the only power source for electric locomotives; therefore, its safe and consistent operation is of critical importance to reliable, high-speed operation. Electrical faults can disrupt train scheduling and jeopardize the safety and security of high-speed railways. Thus, it is essential to quantitatively evaluate possible risk factors in TPSSs. To do so, based on 24-h train timetable, this paper defines indices to describe the failure risk to traction power-supply equipment, and a separate set of indices present the risk from various power-quality problems. Combining both the equipment and power-quality risks yields a comprehensive risk-assessment for the TPSS, by means of a weighted evaluation. The proposed risk assessment method can ensure informed personnel by communicating the system's risk state in real-time to identify high-risk operation, thereby avoiding the potential for severe accidents and informing maintenance and operational plans.
17 April 2017 in IEEE Transactions on Transportation Electrification
Historical catenary trip fault data of China high-speed railway (HSR) revealed that the risk of catenary trip varies distinctively in different time periods and different regions, and catenary trip fault risk has obvious characteristics of time-space differences. In order to represent and quantify the characteristics of risk, this paper proposes a risk index system for catenary lines of HSR considering the characteristics of time-space differences. First, the characteristics of the catenary trip risk and the corresponding reasons are analyzed. Second the risk index system is established from the perspectives of time and space differences. Subsequently, the proposed risk index system is applied to the benchmark data taken from a railway administration in China related to catenary trip records in 3 years. The results of the risk indices are relevant information which can reveal the time-space differences of catenary trip risk, and reflect the influence of external environmental factors as well as catenary's ability of disaster prevention and resilience. This uniform and quantitative information is helpful for the management of the catenary operation risk.
As the core equipment of a traction power supply system, the traction transformer is very important to ensure the safe and reliable operation of the system. At present, the three-ratio method is mainly used to distinguish transformer faults, whereas such a method has some defects, such as insufficient coding and over-general fault classification. At the same time, on-site maintenance personnel make an empirical judgment based on various test data, which is subjective and uncertain to a certain extent. For cases with multiple abnormal data and relatively complex conditions, on-site personnel often need to discuss and even dismantle the transformer to identify the fault, which is time-consuming and costly. In order to improve the effect of fault diagnosis for traction transformer, this paper uses Bayesian network to correlate the cause and effect of various tests and faults. By combining the results of field tests, the fault is diagnosed by the causal probability of the Bayesian network, rather than relying on the exception that occurred in a single experiment to judge its fault. The diagnosis results are more accurate and objective by using the Bayesian network. In this paper, the frequent test anomalies of the traction transformer are taken into account in the network, so that the network can more comprehensively analyze the operation situation of the traction transformer and judge the type of fault. According to field situations, based on the existing set of symptoms of the Bayesian network fault diagnosis, this paper further considers the insulation resistance, dielectric loss tangent value, oil and gas, power frequency voltage, and leakage current. By combining the association rules algorithm and the experience of the field operators, the cause–effect relationship of test data and the conditional probability parameters of the network are obtained. Then, the Bayesian network is constructed and used for traction transformer fault diagnosis. The case study shows that the four types of fault diagnosed using the Bayesian network model proposed in this paper are consistent with the fault types inspected by on-site operators, which shows promising engineering application prospects.
6 August 2018 in IEEE Transactions on Transportation Electrification
A prediction-based maintenance (PBM) strat-egy can save resources while simultaneously guaranteeing the traction power supply system (TPSS) operates in a stable and reliable condition. Based on risk quantification, this work presents a method to assess maintenance needs and op-timize the PBM strategy for traction power supply equip-ment (TPSE). This method utilizes historical maintenance in-formation and the fault record of the TPSE as inputs to a fault prediction model based on a Bayesian classifier. By comparing the prediction results with the actual equipment operation state, statistical parameters are obtained to calcu-late the reliability and economic indices for the maintenance strategies. The comprehensive maintenance risk is then quantified by integrating the dynamic inspection and fault risk costs for the TPSE. The minimum comprehensive risk is selected as the optimization objective, and the criterion for fault prediction spurs from the optimization results are used to form the PBM strategy. Practical maintenance infor-mation and fault record data of 27.5-kV vacuum circuit breakers for a TPSS are used to verify the proposed method. The results show that, by fully utilizing the current data, this method can predict equipment faults by considering multiple factors, and it can quantify the risk for a particular PBM strategy, which is also applicable to similar large-scale trac-tion power supply facilities. To improve the PBM strategy, the approach optimizes fault prediction criteria to achieve a minimum comprehensive maintenance risk. The proposed method can provide effective data and confidence for deci-sion-makers in implementing PBM for TPSS.