A directional overcurrent relay is commonly used to protect the power distribution networks of a distributed system. The selection of the appropriate settings for the relays is an important component of the protection strategies used to isolate the faulty parts of the system. The rapid growth of distributed generation (DG) systems present new challenges to these protection schemes. The effect of solar photovoltaic power plants on relay coordination is studied initially in this research work. A protection strategy was formulated to guarantee that the increased penetration of solar photovoltaic (PV) plants does not affect the relay coordination time. This paper addresses these issues associated with a high penetration of DG through the use of a hybrid protection scheme. The protection strategy is divided into two parts. The first part is based on an optimal fault current limiter value estimated with respect to constraints and the optimal time multiplier setting, and then the coordination time interval is estimated with respect to constraint in Part II. The results of these analyses show that a hybrid protection scheme can effectively handle the complexity of distributed generation (DG) and dynamic relay coordination problems. In this research, three optimization algorithms have been used for calculating the estimated value of impedance fault current limiter () and time multiplier setting (TMS). The response time of hybrid protection schemes is very important. If the computational time of their proposed algorithms is less than their actual computational time, then their response time to address the issue is also less. The performance in all algorithms was identified to arrive at a conclusion that the grey wolf optimized algorithm (GWO) algorithm can substantially reduce the computational time needed to implement hybrid protection algorithms. The GWO algorithm takes a computational time of 0.946 s, achieving its feasible solution in less than 1 s.
In today's scientific scenario the need for reducing power generation cost for minimum fuel used is of utmost importance [1]. One of the important contributors for cost of generation being on the higher side is improper allocation of load(s). In this paper we propose economic dispatch(ED) problem using MATLAB which significantly reduces cost of generation. The MATLAB uses its own in-build library function `fmincon' for execution of divergent non-linear optimization algorithms [2]. The `fmincon' function executes four divergent algorithms namely - i) Sequential Quadratic Programming (SQP); ii) Interior point; iii) Active set; iv) Trust region reflective. In this paper, SQP and interior point algorithms have been employed. Further these algorithms have been employed for cases with outage as well as without outage for IEEE 14 Bus Standard data along with cost coefficients. Basically, this paper is a comparison between optimization capabilities of SQP and interior point and which one is economically profitable with the same amount of load.
Earlier the economic dispatch problem was solved for generation first and subsequently for reserve but nowadays in electricity market these two operations are simultaneously performed to increase the efficiency and reliability of the power system. In this study, MATLAB based optimization solver Sequential quadratic programming (SQP) is used to allocate the static and dynamic dispatch in Electricity market based on price bids submitted by the private and public GENCOS. The idea is implemented on IEEE 17-units system with 57 buses for reserve and energy cost optimization under all operating constraints. The realistic representation of the power system is done where constantly changing load demands, generator outages etc. are included in the model. The SQP algorithm is found to model the practical constraints like ramp-limits, reserve/energy coupling constraints, power-balance and generation capacity limits.
Distributed generation (DG) specifically from solar energy is gaining much attention. Integration of solar photo-voltaic plant (SPP) on distribution grid increases flexibility of the system but lacking behind in terms of convention protection scheme. The impact of orientation of point of common coupling (PCC) of SPP on distribution grid changes the entire power flow computation and hence, coordination of protection devices. This paper presents the power flow computation on modified IEEE 4-bus system for different integrated positions of SPP. Further analysis is carried for the fault current level with different locations and number of SPP DG. It has been found that DG integration increases the magnitudes of fault current; hence, it will have impact on relay co-ordination. A MATLAB/Simulink model is proposed for relay mis-coordination and optimal co-ordination by implementing evolutionary optimization technique. The Proposed study on IEEE 4-bus system along with three units 100 kW capacity of SPP is used to derived optimal co-ordination solution which validates the obtained results on electrical transient’s analysis programming platform (ETAP).