As modern power systems become large and complicated, an automated voltage and reactive power control system is required in most developed countries due to the remarkable recent progress in computer networks and information technology. To date, voltage control has depended on human operators in the Korean power system. Accordingly, this paper proposes a universal intelligent voltage control system for bulk power systems based on sensitivity analysis and a main expert system. A detailed state space modeling technique is discussed, and an effective performance index is proposed to accelerate the searching performance of the expert system. As the searching strategy is an important factor for the speed of the expert system, the least-first search algorithm is applied using this performance index. The proposed system has been applied to the Korean power system, showing promising results.
In this paper, a power system restoration study following a massive or complete blackout was performed. The power system restoration process from a complete shutdown system without the operating generation and load starts with energizing primary restorative transmission systems. During this primary restoration process, unexpected over-voltage may occur due to nonlinear interaction between the unloaded transformer and the transmission system. This is known as the harmonic resonance phenomenon that may cause the burning out of a transformer or other devices. So far, harmonic resonances have been reported in some extra-high voltage systems around the world. Since the harmonic resonance originates from the nonlinear characteristics of the power system components, it is very difficult to predict the occurrence of this phenomenon. This paper reports the analyses of the harmonic resonance that can occur in the Korean power system. In addition, through calculating the required buffer load compared to the length of the line, a solution that changes the length of the restoration path impedance considering the specificity of the Korean system was presented. The various analyses of harmonic overvoltage, including methodologies that are used internationally as comparison groups, are provided based on PSCAD/EMTDC simulations.