Marta Chludzinska

Dr. Marta Chludzinska

orcid

Research Focus & Metrics

Academic Career Length

17Years (2010-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications

1 December 2015 in Building and Environment
Verified
Journal Article
Closed access
PUPiotr Uścinowicz
Piotr Uścinowicz
MCMarta Chludzinska
Marta Chludzinska
ABAnna Bogdan
Anna Bogdan

1 July 2010 in HVAC&R Research
Verified
Journal Article
Closed access
ABAnna Bogdan
Anna Bogdan
MCMarta Chludzinska
Marta Chludzinska
Personal ventilation (PV) is a solution that enables a user to attain full satisfaction from the indoor conditions. It is also a system that—if properly designed—can contribute to the energy efficiency in buildings (i.e., by supplying considerably lower amounts of fresh and treated air indoors). In order to test possible variants of local heating and cooling of a human body by the PV system, a series of tests was conducted. The tests were performed on a thermal manikin and aimed to determine which type of setting (i.e., direction of air supply and temperature of supplied air) causes required cooling/heating of the manikin's surface. The tests were performed with a thermal manikin that helped to determine an equivalent temperature (teq ) of the environment shaped by the PV system. The results revealed that in tests with the nude manikin the PV system decreased the teq value, irrespective of the selected variant of the test. When the manikin was clothed, teq would fall or rise depending on the temperature of supplied air. Tests with a nude manikin demonstrated that the cooling effect was conditioned by the velocity of air supplied from the PV system, rather than by the temperature of the supplied air. In this study, the main parameters affecting teq were thermal insulation of clothing used on the manikin and velocity of air around the manikin.

12 May 2016 in PLOS ONE
Verified
Journal Article
Open access
PDF file
JHJacek Hendiger
Jacek Hendiger
MCMarta Chludzinska
Marta Chludzinska
PZPiotr Ziętek
Piotr Ziętek
This paper presents the results of investigations whose aim was to describe the influence of the pressure difference level on the ability of contaminants migration between neighbouring rooms in dynamic conditions associated with door swing. The analysis was based on airflow visualization made with cold smoke, which simulated the heavy contaminants. The test room was pressurized to a specific level and then the door was opened to observe the trail of the smoke plume in the plane of the door. The door was opened in both directions: to the positively and negatively pressurized room. This study focuses on the visualization of smoke plume discharge and an uncertainty analysis is not applicable. Unlike other studies which focus on the analysis of pressure difference, the present study looks at the contaminants which are heavier than air and on “pumping out” the contaminants by means of door swing. Setting the proper level of pressure difference between the contaminated room and the neighbouring rooms can prove instrumental in ensuring protection against toxic contaminants migration. This study helped to establish the threshold of pressure difference necessary to reduce migration of heavy contaminants to neighbouring rooms.

1 February 2016 in Building and Environment
Verified
Journal Article
Closed access
ABAnna Bogdan
Anna Bogdan
BKBarbara Koelblen
Barbara Koelblen
MCMarta Chludzinska
Marta Chludzinska