5 April 2021 in Energies
Verified
Journal Article
Open access
PDF file
BLBanyat Leelachariyakul
Banyat Leelachariyakul
PYPeerawut Yutthagowith
Peerawut Yutthagowith
This paper presents application of a resonant power frequency converter for high-voltage (HV) and partial discharge (PD) test of a voltage transformer. The rating voltage, power, and frequency of the system are 70 kVrms, 40 kVA, and 200 Hz, respectively. The testing system utilized the converter feeding to an HV testing transformer connected to a conventional partial discharge detection system. The converter system comprising a rectifier and insulated-gate bipolar (IGBT) switches with the H-bridge configuration was applied as a low-voltage source instead of a conventional motor-generator test set which requires large space and high cost. The requirements of the test according to the standards are quality of the test voltage and the background noise level. The required voltage must have the different voltage (DV) and total harmonic distortion (THDv) in the acceptable values of less than 5%. The DV is defined as the difference of the root mean square and peak voltages in percent. The required background noise level must be lower than 2.5 pC. Simulations and experiments were performed for verification of the developed system performance in comparison with those of the previously developed system based on the pulse width modulation converter. It is found that the developed system can provide the testing voltage with the DV and the THDv of lower than 1% and the background noise level of lower than 1 pC. Considering this achievement of promising performance, the developed system is an attractive choice for the HV and PD testing of voltage transformers in real practice.

29 July 2022 in Energies
Verified
Journal Article
Open access
PDF file
BLBanyat Leelachariyakul
Banyat Leelachariyakul
PYPeerawut Yutthagowith
Peerawut Yutthagowith
For high-voltage (HV) and partial discharge (PD) tests on high-voltage equipment, a resonant power frequency converter has recently been developed. A single-phase power frequency converter with a resonant tuning and filter circuit and an HV testing transformer comprise the developed system. A difficulty in the tuning and filter circuit design is the unknown testing system circuit parameters, including unknown parasitic inductance, capacitance, and internal resistance. In this paper, a system with a voltage rating of 75 kVrms, apparent power of 40 kVA, and an operating frequency from 50 Hz to 200 Hz is considered for determination of the equivalent circuit parameters. From the determined circuit parameters, the appropriate resonant tuning and filter circuit was designed effectively. The transfer functions of the input and output testing voltages, along with the transfer impedance of the input voltage and signal voltage of the PD measuring port, were analyzed. The system design was verified by experiments with a voltage transformer. The gain of the transfer impedance was about 15 and 4 at the testing frequencies of 50 Hz and 200 Hz, respectively. With the proper design, it is possible to generate an output voltage waveform that is almost entirely sinusoidal and has a background noise level of under 1 pC. According to the experimental results, the system design of the resonant converter and the method for determining the equivalent circuit are very helpful for the HV and PD tests of voltage transformers in actual practice.