Aiming at the problem of end structure heating caused by the excessive eddy current loss of large synchronous condensers used in ultra-high voltage (UHV) power transmission, combined with the actual operation characteristics of the synchronous condenser, a three-dimensional transient electromagnetic field physical model is established, and three schemes for adjusting the end structure of the condenser under rated condition are researched. The original structure has a copper shield and a steel clamping plate. Scheme 1 has no copper shield but has a steel clamping plate. Scheme 2 has no copper shield but has an aluminum clamping plate. By constructing a three-dimensional fluid–solid coupling heat transfer model in the end of the synchronous condenser, and giving the basic assumptions and boundary conditions, the eddy current loss of the structure calculated by the three schemes is applied to the end region of the synchronous condenser as the heat source, and the velocity distribution of the cooling medium and the temperature distribution of each structure under the three different schemes are obtained. In order to verify the rationality of the numerical analysis model and the effectiveness of the calculation method, the temperature of the inner edge of the copper shield in the end of the synchronous condenser is measured, and the temperature calculation results are consistent with the temperature measurement results, which provides a theoretical basis for the electromagnetic design, structural optimization, ventilation and cooling of the synchronous condenser.
In order to study the multiple restricted factors and parameters of the eddy current loss of generator end structures, both the multi-layer perceptron (MLP) and support vector regression (SVR) are used to study and predict the mechanism of the synergistic effect of metal shield conductivity, relative permeability of clamping plates and structural characteristics of eddy current losses. Based on the eddy current losses of generator end structures under different metal shielding thicknesses and electromagnetic properties, the calculation accuracy of the MLP and SVR is compared. The prediction method gives an effective means for the complex design of the end region of the generator, which reduces the effort of the designers. It also promotes the design efficiency of the electrical generator.
9 November 2021 in IEEE Transactions on Energy Conversion
A new vector-phasor combined with an analytic method for solving complex flux distributions is proposed. The flux leakage and losses in the end region of a 1266 MW scale generator are analyzed by both finite element simulation and an analytical method. The deviation of the calculated result between the analytical model and the finite element method is very small. The analytical model can acquire current data for fast prediction of the flux density. The analytical and numerical results of the flux distribution are found to be in a satisfactory agreement. In addition, the ability to reduce the eddy current losses in the end regions is also researched using various of structural solutions.