The results of the physical modelling of the formation processes of upward discharges from grounded objects in the artificial thunderstorm cell’s electric field are presented. We established the considerable influence of the electrode tip’s radius on the pulse streamer corona stem’s parameters and, subsequently, on the probability of the transformation of the impulse streamer corona first flash’s stem into a first stage of upward leader. We determined the diapason of the optimal tip radii for a lightning rod or lightning conductor, which allows for the most probable formation of the first impulse streamer corona, with the parameters providing the best conditions for the upward leader’s start, the purpose of which is the lowering of the probability of lightning striking the object under protection. A considerable difference between the electrical characteristics of the first impulse corona flash with and without the streamer–leader transition was established. It was shown that the amplitude of the streamer corona flash current impulse is considerable, but not the main defining factor of the streamer–leader transition. It is established that the charge value of the streamer corona first flash is not a threshold requirement for the formation of the upward leader from a ground object, but only defines the probability of the successful upward leader formation. Based on the analysis of the experimental data received, we suggest that there is a dependency between the probability of upward positive leader formation from the grounded objects and the charge value of the first pulse streamer corona flash for the rod (centered) and rope (elongated) lightning conductors and objects in the electric field of the thundercloud and downward lightning leader. The obtained results can be used for mathematical modelling of the formation processes of upward discharges from grounded objects in the artificial thunderstorm’s electric field, as in a natural thunderstorm situation.
The results of a physical simulation using negatively charged artificial thunderstorm cells to test the spectrum of possible electromagnetic effects of upward streamer discharges on the model elements of transmission line monitoring systems (sensor or antennas) are presented. Rod and elongated model elements with different electric field amplification coefficients are investigated. A generalization is made about the parameters of upward streamer current impulse and its electromagnetic effect on both kinds of model elements. A wavelet analysis of the upward streamer corona current impulse and of the signal simultaneously induced in the neighboring model element is conducted. A generalization of the spectral characteristics of the upward streamer current and of the signals induced by the electromagnetic radiation of the nearby impulse streamer corona on model elements is made. The reasons for super-high and ultra-high frequency ranges in the wavelet spectrum of the induced electromagnetic effect are discussed. The characteristic spectral ranges of the possible electromagnetic effect of upward streamer flash on the elements of transmission line monitoring systems are considered.
The results of the experimental application of artificial thunderstorm cells of negative and positive polarities for the investigation of the lightning initiation problems between the thundercloud...
The article represents results of a physical simulation of incomplete upward leader discharges induced on air transmission lines’ elements, using charged artificial thunderstorm cells of negative polarity. The influence of such discharges on closely located model sensors (both of rod and elongated types) of digital monitoring systems, as well as on the models of receiver-transmission systems of local data collection (antennas), was determined. Effect of heterogeneity of electromagnetic field caused by incomplete upward discharges on frequency specter of signals generated on sensors and antennas was estimated. Wavelet analysis was carried out to determine the basic frequency diapasons of such signals. Based on experimental data obtained, suppositions about the extent of influence of nearby incomplete leader discharges on the functioning of currently used systems of transmission lines’ monitoring were made.
Results of an experimental study of processes forming an upward leader discharge from a grounded rod electrode in the electric field of an artificial cloud of charged water aerosol are presented. The transition of the streamer corona flash to an upward leader discharge was found to be of a probabilistic character and to be determined, first of all, not by the current amplitude, and not only by the flash charge passing through the stem of the pulse corona, but by a set of parameters: duration of the current passage at a rather high level and optimum value of the corona charge passed through the stem base. The range of radii of curvature of the rod-shaped lightning arrester tip (from 20 to 25 mm) at which the highest probability of the appearance of an upward leader is observed has been revealed.
The initiation of discharge by model hydrometeors between an artificial-thunderstorm cell (aerosol cloud) of negative or positive polarity and ground has been experimentally studied. It is established for the first time that the conditions of cloud–ground spark discharge initiation by hydrometeors, as well as the characteristics of discharge significantly depend on the polarity of charged cloud. The effect of hydrometeor arrays can be manifested by the cloud–ground lightning initiated in a thundercloud and used for developing scientific principles of artificial lightning discharge.