The article presents a method for detecting earth faults in a compensated medium-voltage network, which can be used especially in fault current passage indicators, but also in standard protection devices. The method is based on the adaptation process of the zero-sequence current protection setting, with the adaptation factor depending on the current value of the zero-sequence voltage. In this article, a comparative analysis of the classical and adaptive zero-sequence current criterion is conducted, taking into account the errors of the measuring system. The results of simulations performed in the PSCad environment are also presented. For a representative set of example short circuits, it was shown that the effectiveness of the presented criterion can be more than 50% higher than that of the standard criteria, taking into account the range of detected transition resistances. A comparison of the proposed method with admittance criteria was also drawn, and it was shown that it is suitable for the detection of high-resistance earth faults.
Common overcurrent criteria used to detect phase-to-phase short circuits in medium-voltage (MV) networks in some cases do not bring the expected results. In particular, this applies to instantaneous overcurrent protections in lines with variable ranges and lines leading to local power plants (LPP), which generate a short-circuit current slightly greater than the rated current. When using overcurrent protections, there are some problems with ensuring the appropriate sensitivity and selectivity. This article proposes a protection based on impedance measurement against the effects of phase-to-phase short circuits in MV lines. The protection can be used at switchgears and also at protection points (PP) located deep in the network. The under-impedance criterion has a range independent of the value of the short-circuit current, and it can be alternative or complement to classic overcurrent protection. The introduction of these criteria allows the protection range to be independent of the type of short circuit and the short-circuit power on the busbar, and to determine this range more precisely. The under-impedance protection is particularly useful in conditions of a growing number of energy sources deep inside the networks and its automation. The main idea was to develop a uncomplicated characteristic that would ensure the possibility of setting the under-impedance protection by people who are not specialists in the field of distance protections. The characteristics have been optimally developed both in terms of the area of detected impedances and easy implementation, operation, and configuration.