The technical rules for connecting turbines to the medium, high or extra-high voltage grid in Germany require the certification of the UVRT characteristics of wind turbines. The state-of-art voltage divider-based test equipment, also named UVRT-Container, is well equipped for executing UVRT tests in field. To conduct the UVRT in field the full wind turbine should be already installed. A second option to perform UVRT tests are system level test benches. They enable the testing of the nacelle. The components that are not actually present, such as the turbine tower or the blades, are emulated via a mechanical hardware in the loop (HiL) system. In this work, for the first time, the performance of two different grid simulators installed at the DyNaLab at Fraunhofer IWES and at the CWD at RWTH Aachen University is compared with a field measurement of the same type of wind turbine. Thus, not only a system test bench measurement is compared to a field measurement. Rather, two system test benches with individual technical approaches are additionally compared with each other. The focus of this work is to investigate the characteristics of the grid simulators within the steady-state range of the UVRT tests to replicate identical fault shapes on the test benches and in the field.
Recently developed nacelle test benches for wind turbines, equipped with multi-physics Hardware-in-the-Loop (HiL) systems, enable advanced testing and even certification of next-generation wind turbines according to IEC61400-21. On the basis of three experiments carried out with a commercial 3.2 MW wind turbine, this paper shows to which extent test bench hardware and HiL systems influence certification results. For the crucial Fault-Ride-Through tests, all deviations were found to be below 1% compared to field and simulation results. For this test, the power HiL system and the accuracy of its impedance emulation are found to be of most relevance. The results for the test items Frequency Control and Synthetic Inertia were found to be more sensitive to shortcomings of the mechanical HiL with its control system. Based on these findings, the paper mentions general procedures to ensure the quality of test benches with HiL systems and, with that, ensure the quality of certification.
Under-voltage ride through (UVRT) tests can be carried out on system test benches, most of them are equipped with a converter based grid simulator. This paper describes the control of the artificial grid impedance at the 4 MW test bench at CWD. Validation measurements with the commercial wind turbine E‑115 E2 show that the virtual impedance specification is sufficient to perform UVRT tests with different grid parameters. Comparative measurements between the voltage divider based FRT Container and the grid simulator with deliberately different grid parameters show a different behavior of the research wind turbine FVA nacelle. Therefore, it is recommended to perform UVRT tests on the test bench with predefined grid parameters.
In recent years, nacelle test benches for wind turbines have been developed internationally. New standards are currently being developed that explicitly refer to the measurement of the electrical properties of wind turbines on these test benches. Thus, they are suitable for measuring the electrical properties required for certification. Another part of the certification is the creation and validation of suitable models of the wind turbine, which are used for stability analyses of the utility grid. Validation requires a suitable model of grid replication on the test benches, which is not yet covered by any applicable standard. Such models should be as simplified a representation of the artificial grid replication as possible to ensure that they are accessible to certification bodies. A model of the grid emulator installed at the CWD of RWTH Aachen University, which was validated with real measurement data, serves as a reference. A step-by-step reduction of the model’s depth up to the system’s technical representation is followed by a model evaluation with respect to the level of detail and an analysis of time and frequency. The evaluation shows that even a highly simplified model consisting of a reference voltage and an impedance replica meets the requirements for the validation of wind turbine models according to IEC 61400-27-2.