As the largest global renewable source, hydropower is a useful supplement to mountainous distribution networks with abundant water resources, and shoulders a large portion of the regulation duty in many power systems. In particular, in the form of decentralized energy sources located to their customers, small hydropower (SHP) improve grid stability by diversifying the electricity system and reducing power loss. The mountainous distribution networks supplied by small hydropower are closed-loop design but open-loop operation, which easily causes the tripping of tie line even further the off-grid operation of small hydropower system. Once the tie line trips, the current countermeasures—such as hydropower shutdown and load shedding—do not fully guarantee the reliability of power supply and the utilization efficiency of hydropower. This paper studies the amplitude-frequency characteristics of SHP off-grid, according to the typical integration of hydropower in South China, a SHP on-grid/off-grid model is established based on the Power Systems Computer Aided Design (PSCAD) platform. It is found that due to the inertia of SHP, the amplitude-frequency characteristics of SHP island system are relatively slow, and the process of non-synchronization with the main grid is gradually expanded. The characteristic of SHP has a certain degree of synchronization with the main grid in the initial island operates stage, which helps to find a novel grid connection method. This paper further proposes the strategy of using fast busbar automatic transfer switch (BATS), which quickly connect the trip-off SHP to the distribution network under the condition of permitting distributed energy grid-connected. The PSCAD simulation results show that proposed strategy has a limited impact on the power grid and prove the effectiveness of the method.
Small hydropower-dominated microgrids enable power exchange with the main grid during grid-connected operation but face frequency stability challenges during sudden islanding (e.g., line faults), requiring prompt generation curtailment or load shedding. In communication-constrained mountainous regions, conventional methods such as high-frequency tripping or low-frequency load shedding often struggle to achieve precise frequency regulation A hierarchical strategy integrating master station centralized decision making and substation local control is proposed. This study theoretically analyzes the post-islanding frequency dynamics of small hydropower microgrids. The master station formulates optimal shedding decisions using regional power flow data, while substations execute decisions via local measurements to mitigate communication issues. A constrained mathematical model is established, solved using a heuristic algorithm, validated through electromagnetic transient simulations, and compared with traditional schemes. The proposed scheme achieves precise surplus capacity shedding, enhancing frequency stability during abrupt islanding with reduced over-/under-tripping compared to that of conventional methods. This hierarchical strategy enhances frequency regulation capability under communication constraints, ensuring reliable operation of small hydropower microgrids during sudden islanding and providing a practical solution for remote regions with limited communication infrastructure.