Working fluids that incorporate solid microencapsulated phase change materials (MPCMs) can benefit from properties such as density and viscosity, which are crucial for improving heat capacity and transfer. However, limited data are available on these parameters for specific slurry and mass ratios. In this study, we present a comparative analysis of the experimental results on the viscosity of three different MPCM aqueous dispersions, namely MPCM 31-S50, MPCM 25-S50, and Micronal 5428X. Varying MPCM mass ratios of distilled water were used to obtain different mass concentrations of the phase change material (PCM), and the resulting slurries were analysed at temperatures ranging from 15 to 40 °C. Our findings showed that all slurries exhibited non-Newtonian characteristics at low shear rates, with viscosity stabilising at higher shear rates, resulting in the characteristics of a Newtonian fluid. The viscosity results were highly dependent on the type of MPCM base dispersion, particularly at high mass ratios, with the slurries having viscosities higher than those of water. Furthermore, we conducted density experiments as a function of temperature, using a flow test setup and a Coriolis flowmeter (Endress+Hauser, Reinach, Switzerland) to determine the density of two MPCMs, namely MPCM 25-S50 and Micronal 5428X. The test samples were prepared at mass concentrations of 10%, 15%, and 20% of the phase change material. We found significant differences in density and viscosity for different MPCM slurries as a result of both the PCM concentration and the material studied. Our results also revealed an apparent PCM phase change process, in which the slurry density significantly decreased in the temperature range of the phase transition from solid to liquid.
Phase Change Material (PCM) is mainly used in thermal energy storage. The addition of small PCM particles to the working fluid circulating in the heat exchange systems allowed to increase the amount of transported energy thanks to the use of latent heat—the heat of phase change. Encapsulating PCM in microcapsules avoids the disadvantages of PCM emulsions and makes the resulting slurry an attractive heat energy carrier. The paper presents the effect of the aggregate state of PCM enclosed in microcapsules on the flow resistance of the slurry through a rectilinear tubular channel. The tests were carried out with the use of a tube with an internal diameter of 4 mm and a measuring section length of 400 mm. A slurry of 21.5 wt.% PCM microcapsules (MPCM) was used as the working fluid in distilled water. A slurry with temperatures of 18.4 °C (PCM encapsulated in a solid state), 26.1 °C (PCM is in a phase change), and 30.5 °C (PCM in a liquid state) flowed through the measuring section. The mass flow rate of the MPCM slurry reached 70 kg/h (Remax = 2150). It was shown that the higher the Re number, the higher the value of the flow resistance, and the more clearly this value depended on the temperature of the slurry. Detailed analyses indicate that the observed changes were not the result of a change in the viscosity of the slurry, but its density depending on the state of the PCM. Significant changes in the density of the slurry in the range of the phase transition temperature are the result of significant changes in the volume of the microcapsule containing the phase change material in different aggregate states.
In this paper, we investigate implications of running a cooling system of two silicagel/water adsorption chillers powered by a district heating network. The devices are connected in series, i.e., the heating water output from the primary chiller is directed to the secondary one. In consequence, the secondary device must deal with an even lower driving temperature and with temperature fluctuations caused by the primary device. We have evaluated three factors that influence the operation of those coupled devices: synchronization of their operating cycles, selection of their cycle time allocations (CTAs), and changing the heating water mass flow rate. Numerical analyses indicate that the performance of the secondary chiller drops significantly if the coupled devices that use the same CTA run asynchronously. The decrease is largest if the shift between the operating cycles is and . We found that it is possible to reduce the negative influence of the asynchronous operation by implementing different CTA in each chiller. The best performance is achieved if the primary chiller uses an adsorption time to desorption time ratio and the secondary chiller uses f = 0.6–0.7.