Generally, utilities regulate the voltage on the long power distribution line within a permissible range by using a step voltage regulator (SVR), which is located around the middle of the line and operates according to the condition of the line current. However, as large-scale distributed generations (DG’s) are interconnected into distribution lines, it is difficult to maintain the line voltage properly owing to bi-directional power flow or reverse power flow. Therefore, this paper proposes a novel SVR tap-changing algorithm to solve the problem, considering line load conditions and reverse power flow. Its validity is verified through the PSCAD/EMTDC software tool and simulations.
The introduction of distributed generation (DG) into distribution systems is expanding due to carbon neutral policies. DG with intermittent output characteristics brings frequent voltage variations in distribution systems. Generally, a step voltage regulator (SVR) is installed in the long distribution line and controls its voltage, which has limits of stable voltage regulations due to the slow tap-changing rate, switching losses, and short life span. To solve those problems, this paper proposes an IGBT-based SVR using zero-voltage switching. It is verified that the stable operation can be obtained through simulation by PSCAD/EMTDC 4.6 software and empirical experiments.
28 February 2024 in Journal of Electrical Engineering & Technology