This article presents local convective boiling measurements in a micro-fin tube for three low global warming potential refrigerants: R448A, R449A, and R452B 1 R452B is the pending ASHRAE designation for the mixture R32/R125/R1234yf (67/7/26), which has the developmental designation DR-55. View all notes . An existing correlation was modified to predict multi-component mixtures, which predicted 98% of the measurements to within ±20%. The new correlation was used to compare the heat transfer coefficient of the three test fluids at the same heat flux, saturated refrigerant temperature, and refrigerant mass flux. The resulting comparison showed that refrigerant R452B exhibited the highest heat transfer, in large part due to its approximately 28% larger liquid thermal conductivity and smaller temperature glide as compared to the tested low-global warming potential refrigerants. For the example case, the heat transfer coefficient for R449A was approximately 8% larger than that for R448A, while the heat transfer coefficient for R452B was more than 59% larger than either R448A or R449A. The heat transfer coefficients for R448A and R449A were roughly between 26 and 48% less than that of R404A for the example case. In contrast, the model predicts that the R452B heat transfer coefficient was approximately 13% larger than that of R404A for the same conditions.
This article is an evaluation of the cycle performance of 39 refrigerants identified in the AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program in a typical air conditioner. This program was initiated in response to environmental concerns raised by the use of high global warming potential refrigerants with the intent to identify and evaluate promising alternative refrigerants. The cycle performance of each refrigerant is calculated assuming the same evaporator heat duty and sink temperatures for the condenser. The evaluation included the effects of heat transfer and pressure drop in the evaporator and the condenser. Four performance variables were investigated: (1) the coefficient of performance, (2) the required volumetric displacement of the compressor, (3) the mean temperature difference of the evaporator, and (4) the compressor discharge superheat. Ratios of the above four parameters relative to the refrigerants that are intended to be replaced are provided for each replacement refrigerant. In addition, a methodology was developed using weighting factors to rank the alternative refrigerants either emphasizing the importance of a large coefficient of performance or the importance of reduced system size. The two ranking methodologies produced different rankings of the alternative refrigerants, although the top three ranked refrigerants had at least two refrigerants in common with each other. Both ranking methodologies identified R1234yf, R32, and R1270 as having ranking factors within those of the best three alternative refrigerants.
1 January 2013 in Journal of Enhanced Heat Transfer
This paper reports vapor-space condensation heat transfer measurements for R123, R134a, and R245fa for the integral trapezoidal fin, and the Turbo-CII geometries on vertical plates. The data consisted of heat flux and wall temperature difference measurements. Condensation heat transfer measurements on a smooth plate agreed well with both measurements and predictions from the literature. Overall, the heat transfer performance of the three refrigerants on the trapezoidal fin was within approximately 8 kW/m(2) of one another. Similarly, the condensation heat flux for R134a and R245fa on the Turbo-CII was within approximately 18 kW/m(2) of each other, while the heat flux of R123 on the Turbo-CII was between 10 and 80 kW/m2 less than that of R245fa. An existing finned tube condensation model was modified to be expressed in terms of the gradient of the condensate curvature with respect to the length of the liquid vapor interface. Curvature gradients for the two surfaces were developed that, when substituted into the modified model, predicted the present measured driving temperature differences for the trapezoidal fin and the Turbo-CII to within 0.4 and 1.2 K, respectively, for all measurements except for R123 on the Turbo-CII surface. With the aid of the curvature gradients, simple models were developed to predict the performance of the trapezoidal, low-finned tube, and the Turbo-C tube. The heat flux to the low-finned tube and the Turbo-C tube were predicted to within 10% and 15%, respectively, of the measured values from the literature for four different fluids.