Thermal conditions of power transformers in abnormal operating conditions such as harmonic loads can be considered as a critical case. In this study, thermal analysis of transformer and additional imposed heat on it, caused by non‐linear loads, are addressed. For this purpose, an appropriate thermal equivalent circuit is used in which temperature of different parts of oil‐immersed power transformers are obtained for harmonic loads. The losses of various components of transformer as heat‐generating sources are estimated. At this end, an appropriate three‐dimensional finite element method is applied to estimate the losses of different parts of transformer. To keep the transformer temperature rise around the permissible value, the transformer is derated. Transformer derating based on the IEEE Std C57.110–2008 recommendation considerably reduces the transformer loading capability. Therefore, this study introduces a new technique for derating of transformer for harmonic loads. This enhances the transformer thermal limits and transformer loading capacity.
Deformation of the windings is one of the main causes of the power transformers failure. Here, for the first time, the electromagnetic forces exerted on the windings are computed in ferroresonance condition and compared with that of the inrush current for a typical power transformer. In both cases, the magnetic core of the transformer saturates and the leakage flux around the windings increases, which leads to large forces on the windings carrying high currents. Therefore, precise modelling of the transformer core is required to calculate the forces inside the transformer. For this purpose, the Jiles–Atherton vector hysteresis model is employed in conjunction with finite element method (FEM) to simulate the laminated grain‐oriented steel core, and then the radial and axial forces inflicted on the windings are estimated.
This study suggests a single switch high step-up DC-DC Converter derived from coupled inductor and switched capacitor used in Grid-Connected Photovoltaic systems. In the suggested converter, a part of the yield voltage is produced by parallel charging of the capacitors on the side of the secondary winding and their series discharge together with the secondary winding. The other part of the output voltage is obtained by simultaneously charging the boost and buck-boost capacitors and discharging them in series with the input voltage source. Finally, these two parts make the output voltage in series, so that high voltage gain with proper duty cycle is obtained. In addition, boost and buck-boost capacitors absorb leakage inductance energy leading to a reduction of the switch voltage stress. As a result, switching losses are reduced and by choosing a switch with lower RDS(ON), conduction losses are also reduced. Finally, a prototype with an output power of 200 Watts, and a voltage conversion of 24–400 Volts was made to confirm the performance in the laboratory, which has the highest efficiency of 95.89%.
2 June 2023 in IET Generation, Transmission & Distribution
This paper proposes a real‐time hot‐spot monitoring method for three‐phase two‐winding oil‐filled transformers under steady‐state conditions, where the corresponding test certificates are not accessible to the customers. For this purpose, the separate determination of iron‐core and copper losses is achieved by real‐time measuring of voltages and currents in both primary and secondary sides and also employing nameplate data of the transformer, including the winding resistances. Subsequent calculations based on IEEE Std C57.110‐2018 provide the top‐oil and hot‐spot temperatures. It is shown that the estimated top‐oil and winding hot‐spot temperatures and also load and no‐load losses match with the measured ones with the maximum difference of 3.5%, 2%, 2.7%, and 9%, respectively.
Due to the necessity of using distributed generation and storage devices in the operation of power systems and with the advancement of technology and industry in the distribution networks, network operators are trying to transform these systems from passive distribution networks to active ones. To this aim, the present study introduces a novel model to exploit an active distribution network from the cost, operation conditions, and reliability points of view. A shared demand management procedure in the presence of storage devices and price-responsive loads is used to improve operational efficiency, and it is presented using a sensitivity matrix. Probability density functions (PDFs) are used to model uncertainty in power generated by wind systems and PVs, and the fuzzy membership function is used to improve the voltage profile of the network. To optimize the objective function, given that the problem goals are not of the same kind, the multi-objective genetic algorithm, based on the non-dominated concept, is implemented. Proposed optimal planning and exploiting of the active distribution network based on the shared demand management procedure, not only maximize profit, because of peak shaving, upgrade deferral, power exchange, and loss reduction but also, technical indexes and reliability improvement are obtained due to energy storage systems (ESS) and price-responsive loads simultaneous management. The rationality and effectiveness of the proposed method are verified by the simulation results of a 33-bus active distribution network.