An integrated energy system that consists of a centralized refrigeration unit can deliver the entire HVAC&R (heating, ventilation, air conditioning, and refrigeration) demand for a supermarket. CO2 (R744) is a natural refrigerant that is becoming increasingly popular for these centralized units due to significant energy and cost savings, while also being sustainable, safe, and non-toxic. This study focuses on the fully integrated CO2 refrigeration system configuration for a supermarket in Porto de Mos, Portugal, which was equipped and fully monitored through the EU-funded project MultiPACK. A dynamic system model was developed in Modelica and validated against measurement data from the site recorded for one week. The model is used to provide additional ejector performance data supporting the obtained measurement data and to evaluate the system configuration at equivalent boundary conditions. The simulation results show that the installation of a vapor ejector (high-pressure lift) is sufficient to improve the efficiency of the unit compared to an ejector-less (high-pressure valve) system. However, more notable enhancements are achieved by including additional flooded evaporation with liquid ejectors and smart regulation of the receiver pressure, adding up to a global efficiency increase of 15% if compared to the high-pressure valve system during the validation week.
A common configuration for transcritical CO2 booster systems in supermarkets involves air conditioning (AC) supplied by cooling a water-glycol circuit. The design capacity of the refrigeration unit must handle all refrigeration loads and the AC load during the hottest summer day, leading to overcapacity and part-load operation for most of the year. A proposed design for implementing cold thermal energy storage (CTES) dedicated to AC demand in a supermarket located in the Oslo region is modeled in the object-oriented language Modelica. Simulation results demonstrate an electricity peak power reduction of up to 32.33%. Even though energy savings are not the primary objective of this project, they are achieved by producing and storing energy when the outdoor temperature is lower, and the coefficient of performance (COP) of the system is higher. The energy savings can reach up to 11.8%. Finally, the economic benefits of the system are assessed under the spot pricing system, revealing potential electricity cost savings of up to 12.56%.