A fire in a marine energy storage system (ESS) has a high risk because of the special situation of the sea compared with land systems. To mitigate serious damage in the event of a fire in marine ESSs, initial suppression of the fire is extremely important. In this study, a unit module-based fire extinguishing system was constructed for the initial suppression of an ESS fire, and a unit module fire suppression test was conducted. In addition, multiple modules were constructed to evaluate the impact of unit module fire suppression on adjacent modules. Novec 1230 and F-500, which are adaptable to ESS fire control, were used as extinguishing agents. The fire suppression test results showed that both extinguishing agents could effectively suppress the ESS fire in the initial stage using the proposed fire extinguishing system. The results of this study will contribute to the development of maritime safety protocols and practical measures for reinforcing preparation for ESS-related fire accidents.