Abnormal heating will reduce the insulation performance of composite insulators or even cause insulator fracture, and the abnormal heating phenomenon is more serious under high-humidity conditions. Therefore, in this paper, the voltage withstand test of abnormal heating composite insulators caused by aging and damp sheath, decay-like core rod, and contamination were carried out under different ambient humidity. The heating and discharge of composite insulators were observed by infrared thermal imager and ultraviolet imager, and its temperature characteristics were analyzed from the aspects of heating range, heating shape, and temperature difference. In addition, in order to study the abnormal heating mechanism of composite insulators, the micro-morphology, chemical groups and dielectric properties of the silicon rubber of composite insulators with aging and damp sheath and the decay-like core rod were also measured. It is found that the temperature characteristics of the three types of abnormal heating composite insulators are different, and the temperature difference increases with the increase of humidity. The deterioration of silicone rubber and core rod material is the internal reason for the abnormal heating of composite insulators, and high-humidity conditions will exacerbate the heating phenomenon.
While direct current (DC) ice-melting is currently adopted for some transmission lines, its application to 10 kV distribution transformers—often located in remote and rugged terrain—presents significant operational challenges. Disconnecting these transformers prior to ice-melting is a complex procedure that incurs substantial labor, material, and financial costs. Leaving transformers connected risks DC current flowing into idle windings, potentially causing damage. Furthermore, existing mobile DC ice-melting power supplies are bulky and impose stringent transportation requirements, rendering them unsuitable for use on mountain roads. To overcome these limitations, this paper proposes a compact, lightweight variable-frequency ice-melting device. The operating principle and output characteristics of the variable-frequency method are investigated in detail. Using Simulink, system modeling and simulation analyses are performed to obtain the voltage and current output characteristics, along with harmonic spectra. Simulation results demonstrate that the proposed device achieves significant miniaturization compared with conventional solutions: within the typical parameter range of conventional devices, the volume can be reduced by 44–58% and the weight by 43–52%. In addition, the selected LC filter parameters (L = 10.39 mH, C = 86.62 μF) represent an optimized compromise solution that effectively suppresses input harmonics while maintaining the output current total harmonic distortion (THD) within an acceptable limit of 3.6%. Experimental results further validate the feasibility of the variable-frequency ice-melting current. Based on a matrix converter topology, the proposed device enables flexible adjustment of the output melting voltage and frequency, exhibits excellent low-frequency performance and dynamic response, and maintains low output harmonic content—fully meeting the application requirements for variable-frequency ice-melting. The key novelty lies in a compact matrix-converter-based de-icing device with systematic low-frequency performance analysis, offering superior portability and adaptability over traditional DC solutions.