In the Republic of Korea, the 2030 Nationally Determined Contributions aim for carbon neutrality by 2050, with the building sector targeting a 32.8% reduction in carbon emissions by 2030 compared with the 2018 baseline. To achieve these goals, significant efforts are underway to improve the energy efficiency of buildings. Building energy simulation is a standard method for evaluating energy performance as it assesses the current performance and predicts the potential contributions of energy retrofitting initiatives. However, industrial factories often lack specific energy simulation profiles, posing a challenge for accurate energy performance assessment. This case study aims to bridge this gap by investigating a detailed building profile for factory building based on the extended operational data and experimental measurements within a live factory setting. Energy simulations employing these factory-specific profiles yielded R2 values (coefficient of determination) of 98.2% and 94.1% for cooling and heating energy accuracy, respectively, when compared with the actual monthly consumption data. Additionally, simulations with these profiles demonstrated a 2.81% improvement in R2 accuracy compared to those using conventional office building profiles, particularly enhancing the precision during the cooling season. These findings highlight the effectiveness of customized profiles in building energy simulations, ensuring more precise and reliable energy efficiency assessments.
This study investigates a Proxy-Calibration method for modeling Variable Refrigerant Flow (VRF) systems in TRNSYS, addressing the absence of a dedicated simulation component. The approach approximates part-load behavior through indoor-unit combination mapping, utilizing empirical data from a public office building in Seoul. Simulation results were compared with one year of monitored data. While indoor temperature trends showed moderate agreement (R2 = 0.68), electricity consumption diverged significantly from actual measurements. The coefficient of variation in the root mean square error (CVRMSE) ranged from 95% to 118% for the boiler and 153% to 590% for the VRF system, indicating a substantial discrepancy well beyond standard calibration thresholds. These findings underscore the limitations of using static performance maps without explicit control logic. Consequently, this study defines the proposed method as an exploratory investigation; while it establishes a procedural framework for approximating VRF operation, rigorous energy prediction requires further refinement through empirical curve fitting and detailed control representation.