In this study, a new submersion detection sensor with improved reliability and stability is proposed. The new sensor uses two Resistance Temperature Detectors (RTDs) and operates on the thermal equilibrium principle. The submersion detection sensor controls two RTDs that maintain a constant temperature difference between them in the surrounding environment. The first RTD is used as a reference sensor to measure ambient temperature and the second RTD is supplied with higher current than the reference sensor for self-heating. When submerged, because the thermal conductivity and convective heat transfer coefficient of water are higher than that of air, the temperature difference between the two RTDs is lower in water than in air based on the thermal equilibrium principle. Under these conditions, a submersion detector with a signal conditioning circuit detects these temperature differences. The static performance of the proposed sensor was evaluated by checking whether malfunctions occurred at varying ambient temperatures, differing humidities, and when there was rainfall. In addition, the dynamic performance was evaluated using the response time at varying ambient air temperatures before submersion and with changing water temperatures after submersion, as a metric. The proposed submersion detection sensor is expected to find useful application in aircrafts, ships, and various other industrial fields.
In this study, a low-cost surge current detection sensor (SCDS) that can measure high current surges using a low-current toroidal coil is proposed for maintenance of a surge protective device (SPD). The proposed SCDS is designed to display the predicted lifetime of the SPD based on the magnitude of surge current and number of surges. In addition, a method for measuring high surge current using a toroidal coil that can usually measure only low current is proposed. A lightning strike counter consists of a microcontroller with a low-power liquid crystal display (LCD) driver, 3 VDC lithium battery, and signal conditioning circuit that converts amplitude information of the surge current into duration information of a negative pulse to facilitate processing in the microcontroller. In this paper, we propose a software algorithm that can calculate the remaining lifetime of SPD based on the amplitude and number of surge currents. There is also an option to select the capacity of the surge protective device and the number of phase lines, allowing it to assess the predicted lifetime for various types of Class II SPDs. The proposed SCDS is measured as 7.2 μA from the battery power consumption test, and the service life is calculated to be 11.1 years. It meets the International Standard IEC62561-6 test conditions of the lightning strike counter and is expected to be useful in the maintenance of SPDs and lightning protection systems.
Lightning strikes can cause significant damage to critical infrastructure and pose a serious threat to public safety. To ensure the safety of facilities and investigate the causes of lightning accidents, we propose a cost-effective design method for a lightning current measuring instrument that uses a Rogowski coil and dual signal conditioning circuits to detect a wide range of lightning currents, ranging from hundreds of A to hundreds of kA. To implement the proposed lightning current measuring instrument, we design signal conditioning circuits and software capable of detecting and analyzing lightning currents from ±500 A to ±100 kA. By employing dual signal conditioning circuits, it offers the advantage of detecting a wide range of lightning currents compared to existing lightning current measuring instruments. The proposed instrument has the following features: First, the peak current, polarity, (front time), (time to half value), and Q (amount of energy of the lightning current) can be analyzed and measured with a fast sampling time of 380 ns. Second, it can distinguish whether a lightning current is induced or direct. Third, a built-in SD card is provided to save the detected lightning data. Finally, it provides Ethernet communication capability for remote monitoring. The performance of the proposed instrument is evaluated and validated by applying induced and direct lightning using a lightning current generator.
Technical issues on measuring the low residual voltage (Vres) in SPD determined in international standards are reviewed. The SPD for power supplies represents residual voltages more than 1.5kV but the SPD for applications in low voltage data, communications and signaling circuits shows several tens ~ hundreds volts. Thus, it is necessary to determine detailed technical specifications in a technical standard for implementing its accurate measurements. However, there are no such detailed specifications in international standards and that may cause confusions in operating a certification system based on the international standard for SPD performance. Therefore, in this study, technical issues on international standards for measuring the low residual voltages of SPD are reviewed.