Despite being discovered more than 20 years ago, nanofluids still cannot be used in the power industry. The fundamental reason is that nano-insulating oil has poor stability, and its electrical performance decreases under negative impulse voltage. We found that C60 nanoparticles can maintain long-term stability in insulating oil without surface modification. C60 has strong electronegativity and photon absorption ability, which can comprehensively improve the electrical performance of insulating oil. This finding has great significance for the industrial application of nano-insulating oil. In this study, six concentrations of nano-C60 modified insulating oil (CMIO) were prepared, and their breakdown strength and dielectric properties were tested. The thermally stimulated current (TSC) curves of fresh oil (FO) and CMIO were experimentally determined. The test results indicate that C60 nanoparticles can simultaneously improve the positive and negative lightning impulse and power frequency breakdown voltage of insulating oil, while hardly increasing dielectric loss. At 150 mg/L, the positive and negative lightning impulse breakdown voltages of CMIO increased by 7.51% and 8.33%, respectively, compared with those of FO. The AC average breakdown voltage reached its peak (18.0% higher compared with FO) at a CMIO concentration of 200 mg/L. Based on the test results and the special properties of C60, we believe that changes in the trap parameters, the strong electron capture ability of C60, and the absorption capacity of C60 for photons enhanced the breakdown performance of insulating oil by C60 nanoparticles.
The premature failure phenomenon that occurs in solid insulation under the application of repetitive impulse voltages is known as the accumulative effect of impulse voltages on a solid dielectric. The accumulative failure of winding insulation is considered to be a core problem resulting from this phenomenon. The main problems include the accumulative failure of motor winding insulation under pulse‐width modulation impulses and the accumulative failure of transformer winding insulation under the application of overvoltages, and these problems represent new challenges in the safe and stable operation of power grids. With regards to the above problems, this study reviews the results of recent research on the accumulative failure characteristics and mechanisms of winding insulation when subjected to repetitive impulse voltages. The challenges faced are discussed at the end of this study.
Faults on the dc line threaten the stability and reliability of the modular multilevel converter based HVDC (MMC-HVDC) systems. Fault current limiting is one of the crucial steps to handle the dc line fault. In this paper, a mutual-inductance-type fault current limiter (MFCL) using coupled reactors and few power electronic switches is proposed. Compared with the conventional dc reactors, it can automatically limit the fault current during the current rising stage with an increased equivalent inductance and accelerate the decline of the current by reducing the inductance of the discharge circuit. Consequently, the fault current stress and the total capacity of required arresters are decreased. Compared with the existing power electronic-type fault current limiters, the proposed MFCL provides an inexpensive and potential solution to the suppression of dc fault current using simple fault current limiting topology with fewer power electronic switches. The simulation case study and experimental tests are carried out to verify the performance and practicality of the proposed MFCL.