Sparse modular multilevel converters (SMMCs) are a new type of lightweight high-voltage large-power AC/AC converter that significantly reduces the number of components compared to modular multilevel matrix converters (M3Cs). This study proposes a fault ride through a control strategy for SMMC to address the issues of arm energy imbalances and valve-side overvoltage, which occur during asymmetric faults on the low-frequency side. First, we establish models of the energy deviation of the arms under asymmetric short-circuit faults on the low-frequency side of SMMC. We also study the influence mechanism of the control strategies on the arm energy imbalance during faults. On this basis, an arm energy balancing strategy based on zero-sequence voltage injections combined with AC voltage control is proposed; this can achieve arm energy balance and suppress the negative sequence current and overvoltage of the SMMC. Finally, we construct a simulation model of an offshore wind power low-frequency transmission system based on the SMMC. The simulation results show that the proposed energy balance strategy can realize the stable operation of the low-frequency transmission system (LFTS) under asymmetric faults on the low-frequency side, that the maximum capacitor voltage deviation during the fault does not exceed 10% and that capacitor voltage returns to normal 0.25 s after the fault occurs.
A diode-based rectifier (DR) is an attractive transmission technology for offshore wind farms, which reduces the volume of large bulk platforms. A novel parallel–series DC wind farm based on a distributed DR is proposed, which meets the requirements of high voltage and high power with an isolation capability from other units. The coupling mechanism between a modular multilevel converter (MMC) and a DR has been built, and the coordinate control strategy for the whole system has been proposed based on the MMC triple control targets with intermediate variables. Under the proposed control strategy, the system automatically operates at maximum power point tracking (MPPT). The feasibility of topology and the effectiveness of the control strategy are verified under start-up, power fluctuation, onshore alternating current (AC) fault, and direct current (DC) fault based on the power systems computer-aided design (PSCAD)/electromagnetic transients including direct current (EMTDC) simulation.