External insulation of coastal power grids faces harsh conditions and is highly susceptible to flashover. Currently, technologies for online monitoring and flashover early warning are severely lacking. As a reflective passive sensing device, Fiber Bragg Grating (FBG) enables the monitoring of surface discharge and provides an early warning for flashover on external insulation. A 10 kV fiber-optic composite insulator was developed in this study. A linear relationship between the FBG central wavelength and interfacial temperature was established through temperature calibration experiments. Coastal salt fog conditions were simulated in an artificial fog chamber, where AC pollution flashover tests were performed on the fiber-optic composite insulator. FBG central wavelength and visible images of discharge were synchronously acquired during experimentation. Experimental results indicate that the interfacial locations on FBGs where the temperature increases during flashover coincide with the positions of visible discharge arcs, demonstrating the effectiveness of the monitoring method. A temperature rise rate of 4.88 × 10−2 °C/s was found to trigger flashover warning, while a rate of 4.96 × 10−2 °C/s initiated trip protection. A discharge-region ratio characteristic was proposed for visible discharge images based on highlight area ratio, R-channel deviation, and mean saturation features. This characteristic serves as a flashover warning when its value reaches 46.7%. This study provides a novel research approach for online monitoring and flashover early warning of external insulation in coastal salt fog environments.
External insulation of coastal power grids transmitting offshore wind power faces significant threats from salt fog flashovers. Current arc monitoring and early warning technologies for flashover are severely inadequate. Research on salt fog discharge processes and determining the threshold at the flashover brink for transmission equipment external insulation is crucial for ensuring the safe operation of coastal grids delivering offshore wind power. Fiber Bragg Grating (FBG), with its advantages of compact size, excellent insulation, and fast response, enables effective discharge monitoring and identification of the critical flashover state on external insulation surfaces. In this study, FBGs were embedded at the interfaces of typical external insulation specimens, including silicone rubber plates and epoxy resin plates, to conduct contaminated AC salt fog discharge tests. Synchronized measurements of visible light images, infrared thermal images, and FBG interface temperature were conducted to investigate the discharge physical processes on silicone rubber insulating surfaces and the flashover threshold based on FBG temperature rise rate. The results indicate that discharge process can be divided into three phases: arc initiation, extension, and flashover based on the characteristics of arc visible light images. By comparing arc locations in infrared and visible light images with the corresponding FBG interface temperature rise, the arc phase criterion of FBG interface temperature rise rate and position were proposed. Furthermore, through multiple experiments, it has been found that flashover occurs when both interface temperatures reached above 4.6 × 10−2 °C/s. This study provides a novel research methodology for physical process of external insulation discharge and flashover warning in coastal salt fog environments.