Partial discharge (PD) fault diagnosis is of great importance for ensuring the safe and stable operation of power transformers. To address the issues of low accuracy in traditional PD fault diagnostic methods, this paper proposes a novel method for the power transformer PD fault diagnosis. It incorporates the approximate entropy (ApEn) of symplectic geometry mode decomposition (SGMD) into the optimized bidirectional long short-term memory (BILSTM) neural network. This method extracts dominant PD features employing SGMD and ApEn. Meanwhile, it improves the diagnostic accuracy with the optimized BILSTM by introducing the golden jackal optimization (GJO). Simulation studies evaluate the performance of FFT, EMD, VMD, and SGMD. The results show that SGMD–ApEn outperforms other methods in extracting dominant PD features. Experimental results verify the effectiveness and superiority of the proposed method by comparing different traditional methods. The proposed method improves PD fault recognition accuracy and provides a diagnostic rate of 98.6%, with lower noise sensitivity.
A mechanical vibration fault diagnosis is a key means of ensuring the safe and stable operation of transformers. To achieve an accurate diagnosis of transformer vibration faults, this paper proposes a novel fault diagnosis method based on time-shift multiscale increment entropy (TSMIE) combined with CatBoost. Firstly, inspired by the concept of a time shift, TSMIE was proposed. TSMIE effectively solves the problem of the information loss caused by the coarse-graining process of traditional multiscale entropy. Secondly, the TSMIE of transformer vibration signals under different operating conditions was extracted as fault features. Finally, the features were sent into the CatBoost model for pattern recognition. Compared with different models, the simulation and experimental results showed that the proposed model had a higher diagnostic accuracy and stability, and this provides a new tool for transformer vibration fault diagnoses.