This paper presents a hierarchical coordinated con-trol strategy designed to enhance the overall performance of the energy storage system (ESS) in secondary frequency regulation (SFR). The strategy includes three layers: the system layer, the ESS operation layer, and the coordination control layer. In the system layer, a detailed frequency response model of the multi-area interconnected system is developed. The intrinsic mech-anisms of timing, depth, and the effect of ESS and conventional generating unit (CGU) in SFR are revealed through the sen-sitivity analysis of the power allocation factor. Furthermore, a sensitivity-based adaptive power allocation strategy for ESS and CGU is proposed, which improves the SFR effect while reducing the ESS power and maintaining the state of charge (SOC). In the ESS operation layer, the ESS is divided into two components for integration, employing a monotonic charge-discharge strategy to reduce lifetime degradation caused by frequent charging and discharging, thereby enhancing operational efficiency. In the coordination control layer, considering the power prediction and the ESS operating state, a SOC optimization strategy based on the double-input fuzzy control (DIFC) is proposed. It further dynamically corrects the power allocation factor based on fuzzy rules, optimizing the SOC level to ensure the bidirectional SFR capability of ESS under all conditions. The case studies validate the overall SFR performance of the proposed strategy with different scenarios.
In response to the issues of subjective weighting of indicators and insufficient consideration of the temporal dimension of risk factors in current operational safety risk assessments for electric utilities, this paper proposes a method for assessing operational safety risks in electric utilities based on the Accident-Calibrated Cumulative Risk Index (ACCRI). First, in accordance with current standards and operational guidelines, a multi-level indicator system covering four dimensions, namely human resources and personnel behavior, equipment and facilities, environment and conditions, and management and systems, is established to provide a systematic characterization of operational safety risks in electric utilities. On this basis, the ACCRI is defined by weighted accumulation of the average risk exposure values of tertiary indicators within their characteristic periods. Historical accident sample importance is used to calibrate and identify tertiary indicator weights and characteristic periods, thereby reducing the subjectivity of traditional expert-based weighting. Furthermore, considering the differing temporal-scale characteristics of various risk indicators, a characteristic-period identification model is established and solved using an improved sparrow search algorithm to balance the timeliness and accuracy of risk assessment. By incorporating chaotic initialization, Gaussian mutation, and adaptive weighting mechanisms, this algorithm enhances population diversity and balances global search capability with local optimization capability across different solution stages, thereby improving the solution efficiency and accuracy of the model. Finally, the case study preliminarily demonstrates that the proposed method can characterize the temporal-scale differences among risk factors and shows potential for engineering application under the available enterprise data.