Nowadays, high voltage circuit breaker (CB) simulations are mostly based on Computational Fluid Dynamics (CFD) models. Such simulations require significant computer resources. An alternative approach is to use enthalpy flow models, which do not use space discretization of the interrupter unit chambers and valves. Gas flow is calculated based on state of gas in adjacent chambers and valve settings. However, the valve shape has significant influence on the effective flow cross section between chambers. Therefore, in order to ensure correct simulation results, it is necessary to determine the correct values of discharge coefficients for all valves in the interrupter unit of a circuit breaker. In this paper, the discharge coefficients were determined by combining a series of CFD and enthalpy flow simulations for each valve in the interrupter unit. After that, discharge coefficients are used as input for further simulations based on the enthalpy flow model. This way, benefits from both models are combined: more precise gas flow calculation and faster simulations. The proposed novel approach is validated in a high-power laboratory by pressure measurements on a 420 kV 63 kA self-blast circuit breaker.
Special attention needs to be given to the processes that occur in alternating current arcs at the instant when the current naturally passes through a zero. The short interval of time around current zero, named the "interaction period" [1], is of crucial importance for arc-quenching, when it is decided whether the interruption will be definite or whether arc reignition will occur. As a matter of fact, regardless of the SF6 circuit breaker working principle, its rated voltage and history of the short circuit current interruption process, there is a critical value of arc extinction voltage peak which must be reached to make a successful interruption possible [2]. The arc extinction voltage peak can be increased by elongating the arc (in other words by increasing the distance between arcing contacts) and/or by increasing the pressure of SF6 gas inside the thermal chamber around current zero instant. This means that it is possible to find a critical value of distance between arcing contacts and a critical value of SF6 gas pressure inside the thermal chamber at current zero instant as criteria for successful short circuit current interruption. Based on the results of type tests in high power laboratory (including current zero measurement - CZM) and the calculation results of the software HV CB Simulation, these criteria for short circuit current interruption are successfully established for a real SF6 circuit breaker 245 kV 40/50 kA.
This paper presents the design and development of a distributed measurement system for measuring pressure in high voltage circuit breakers (HV CB) and other switching apparatuses, during no-load operations. Instead of using traditional pressure transducers which require significant installation space, additional data acquisition cards and often demand for complex wiring, an in-house solution of pressure measurement is proposed. The system consists of miniature sensors, accompanied with a suitable amplifier, microcontroller unit and communication module, which may be distributed inside the interrupter unit in convenient locations. Due to the fact that the measurement values are transmitted digitally, measurement noise is significantly reduced while the wiring of the system is additionally simplified. The proposed measurement system is tested using two different interrupters (HV CB and a load break switch). The experimental results have demonstrated that the developed system is applicable, accurate, cost-effective, flexible and simple to use.
Arc conductance decay is a well-established performance indicator for thermal interruption in SF6, with a narrow range of known limit values. It is also shown that conductance decay can also serve as a performance indicator in CO2-based mixtures, although different limit values for successful thermal interruption apply. In this publication, values of arc conductance 200 ns before current zero are presented for a large number of experiments performed in CO2/O2 90/10 mixture under short line fault-like conditions. These measurements are used to establish limit values for the CO2/O2 mixture, and to investigate the pressure dependence of conductance decay.