The solar–air source heat pump (S-ASHP) system is used to prepare domestic hot water and is an important form of hot water preparation in many colleges and universities in China. However, the traditional design specifications and operation control strategies can cause excessive design capacity for the hot water system and energy waste. To address these issues, in this study, we integrate the S-ASHP hot water system with predictive modeling of user demand, proposing two distinct control strategies for the hot water supply system. Scheme I: The traditional hot water demand specification is used for design, and the feedback control strategy of the end hot water demand is set according to a fixed mode. Scheme II: A feedforward–feedback combined control strategy based on the ANN-LSTM-STA model is used to predict water consumption and set the end hot water demand. Compared with Scheme I, Scheme II shows significant advantages in heat supply, total energy consumption, and coefficient of performance (COP). The heat supply of the solar collector (SC) supply system is increased by 9.47%, the heat supply of the ASHP supply system is significantly reduced by 57.52%, the running time is reduced by 33.45%, the pump’s energy usage decreases by 16.65%, and the overall system energy consumption drops by 43.85%. Additionally, the coefficient of performance (COP) improves by 6.42%, and the coefficient of performance of the system (COPsys) sees a significant increase of 18.39%.