Hybrid renewable energy systems (HRES) that put solar, wind, and battery storage under one control scheme are widely presented as the way to keep an inverter-dominated grid stable, yet many studies describe their simulations only in words and report summary indicators without the dynamic quantities that actually decide stability. This paper supplies those quantities through three linked, fully specified studies on named test systems. A reduced-order system-frequency-response model measures the rate of change of frequency (RoCoF), the nadir, the settling time, and the steady-state deviation for four strategies (uncoordinated, adaptive droop, virtual inertia, and a coordinated model-predictive-plus-virtual-inertia scheme) under a contingency, across a penetration sweep, and in a 300-trial Monte-Carlo with one-way ANOVA. A receding-horizon model predictive control (MPC) scheduler is then compared against a greedy rule on curtailment, unserved energy, cost, state of charge, and forecast robustness. A Volt/VAR study on the IEEE 33-bus feeder measures daily voltage fluctuation under real AC power flow. The central finding is metric-dependent and corrects a common belief: adaptive droop, ranked best by summary metrics, does not reduce RoCoF at all (it stays at 2.50 Hz/s, crossing a 1 Hz/s grid-code limit above about 40% penetration), because RoCoF at the instant of a disturbance is set by inertia alone, and only virtual inertia lowers it (to 0.50--0.63 Hz/s). The MPC does not cut curtailment, which is storage-bound, but removes unserved energy (0.77 to 0.00 MWh/day), cuts cost by 37%, and holds the frequency-reserve band on 100% of days against 0% for the greedy rule. Coordinated Volt/VAR cuts the daily voltage swing by 11 to 26%, and the ANOVA confirms every frequency difference at p<10^-6. Results are reported as they came out, including the cases that contradict common assumptions.