Abdelrahman Mohamed Mohamed

Mr. Abdelrahman Mohamed Mohamed


Research Focus & Metrics

Academic Career Length

1Year (2026-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
9 November 2026 in Preprints.org
Verified
Preprint
Open access
PDF file
SGShady Gomaa
Shady Gomaa
AMAbdelrahman Mohamed Mohamed
Abdelrahman Mohamed Mohamed
HMHassan M. Maaly
Hassan M. Maaly
YIYasser Ibrahim
Yasser Ibrahim
MNMahmoud Nawar
Mahmoud Nawar
The flexural capacity of composite cold-formed steel (CFS) beams is often limited by premature instability of the thin-walled section, so that the compressive capacity of the slab is not fully used. This paper examines which measures remove that limit and when a higher concrete grade becomes worthwhile. A nonlinear finite element model, validated against three full-scale tests, was used in a parametric study of thirty beams. The variables were the slab cross-section, the CFS profile, the concrete grade, the type and spacing of plate shear connectors, and stiffening by web stiffeners and a lower-flange plate. Four failure modes were identified, and the toughness followed their hierarchy rather than the ranking of peak loads. At equal self-weight a hollow slab raised the peak load by 37%, and inverting the lips of the channel raised it by 78% while making the connector spacing almost irrelevant. Web stiffeners raised the toughness by up to 124%, against 27% for a lower-flange plate that gave the higher strength. Raising the grade from C30 to C60 was worth 6.6% in peak load while the section buckled locally but 12.9% once stiffened: high-performance concrete pays only after the instability of the steel section is suppressed.