Nonlinear systems of equations in complex plane are frequently encountered in applied mathematics, e.g., power systems, signal processing, control theory, neural networks, and biomedicine, to name a few. The solution of these problems often requires a first- or second-order approximation of nonlinear functions to generate a new step or descent direction to meet the solution iteratively. However, such methods cannot be applied to functions of complex and complex conjugate variables because they are necessarily nonanalytic. To overcome this problem, the Wirtinger calculus allows an expansion of nonlinear functions in its original complex and complex conjugate variables once they are analytic in their argument as a whole. Thus, the goal is to apply this methodology for solving nonlinear systems of equations emerged from applications in the industry. For instances, the complex-valued Jacobian matrix emerged from the power flow analysis model which is solved by Newton-Raphson method can be exactly determined. Similarly, overdetermined Jacobian matrices can be dealt, e.g., through the Gauss-Newton method in complex plane aimed to solve power system state estimation problems. Finally, the factorization method of the aforementioned Jacobian matrices is addressed through the fast Givens transformation algorithm which means the square root-free Givens rotations method in complex plane.
Phasor measurement units (PMUs) lose GPS time and enter holdover on a local oscillator, whose drift rotates every reported phasor. How long holdover can last before generator dynamic state estimation degrades remains unquantified. We study an extended Kalman filter on the IEEE 39-bus system against an ANDES simulation with stochastic loads and field-level PMU noise, under a pre-specified analysis plan. We derive a closed form for the share of PMU phase drift reaching rotor-angle estimates; it matched all 21 tested cases within 3%. This share depends on the filter’s weighting of active power against voltage angle. With noise variances calibrated to the innovations, a drifting PMU passed up to 3.0 times its phase error into the rotor angles. With compensated quartz, the error reached 0.005 rad (0.29°) after 3.5–11 min, before the PMU’s own angle error (14.7 min). Weighting power more heavily cut the pass-through 13–32-fold at the simulated locations and had the lower no-drift error (2.4 against 3.2 mrad). A clock-aware filter removed drift at some cost in ambient accuracy; with power measurements, an innovation test detected every simulated single-PMU drift without holdover flags. Holdover tolerance depends on the estimator’s weighting as much as on the oscillator.