The electromechanical impedance (EMI) technique is considered to be one of the most promising methods for developing structural health monitoring (SHM) systems. This technique is simple to implement and uses small and inexpensive piezoelectric sensors. However, practical problems have hindered its application to real-world structures, and temperature effects have been cited in the literature as critical problems. In this paper, we present an experimental study of the effect of temperature on the electrical impedance of the piezoelectric sensors used in the EMI technique. We used 5H PZT (lead zirconate titanate) ceramic sensors, which are commonly used in the EMI technique. The experimental results showed that the temperature effects were strongly frequency-dependent, which may motivate future research in the SHM field.
7 August 2009 in IEEE Transactions on Instrumentation and Measurement
Recent research has shown that electromechanical (E/M) impedance-based techniques are an efficient strategy for damage sensing in the context of structural health monitoring (SHM). The basic principle is to excite the lead zirconate titanate (PZT) sensors attached to the structure and to measure the corresponding electrical impedance. A variation in the electrical impedance indicates a variation in the mechanical impedance and, consequently, structural damage. To measure the electrical impedance, most universities and research centers use expensive, bulky, heavy, and high-powered impedance analyzers, which limit new developments and practical applications. To overcome these issues, this paper presents an efficient and inexpensive methodology for electrical impedance measurement. To verify the efficiency and accuracy of the new methodology, practical tests were carried out, and the results were compared with those obtained using a conventional impedance analyzer.
Power transformers are crucial in an electric power system. Failures in transformers can affect the quality and cause interruptions in the power supply. Partial discharges are a phenomenon that can cause failures in the transformers if not properly monitored. Typically, the monitoring requires high-cost corrective maintenance or even interruptions of the power system. Therefore, the development of online non-invasive monitoring systems to detect partial discharges in power transformers has great relevance since it can reduce significant maintenance costs. Although commercial acoustic emission sensors have been used to monitor partial discharges in power transformers, they still represent a significant cost. In order to overcome this drawback, this paper presents a study of the feasibility of low-cost piezoelectric sensors to identify partial discharges in mineral insulating oil of power transformers. The analysis of the feasibility of the proposed low-cost sensor is performed by its comparison with a commercial acoustic emission sensor commonly used to detect partial discharges. The comparison between the responses in the time and frequency domain of both sensors was carried out and the experimental results indicate that the proposed piezoelectric sensors have great potential in the detection of acoustic waves generated by partial discharges in insulation oil, contributing for the popularization of this noninvasive technique.
1 July 2011 in Mechanical Systems and Signal Processing
This paper presents a performance assessment of macro fiber composite (MFC) sensors for measuring acoustic emission (AE) signals from partial discharges (PD) in power transformers filled with mineral oil. MFC sensors are low-profile and flexible, allowing them to be attached to uneven surfaces, such as a transformer wall. Two types of MFC sensors were assessed: P1 (d33 effect) and P2 (d31 effect), which are optimized for different deformations in the structure, such as elongation and contraction, respectively. In addition, a conventional AE sensor, R15I-AST model from Physical Acoustics South America, was also used as a reference for comparative analysis. Four metrics were applied to the signals: root mean square, energy criterion, Akaike criterion, power spectral density, and correlation. The experimental results indicate a high similarity between the MFC sensors and the conventional AE sensor, which expands the research field in acoustic PD measurement in power transformers by using low-cost and flexible sensors.
The pencil lead break (PLB) is a well-known method for characterizing acoustic emission sensors. In this paper, we analyze the effectiveness of this method in characterizing piezoelectric transducers for structural health monitoring (SHM) systems based on the electromechanical impedance (EMI) technique. Tests were carried out on aluminum beams of different sizes, and two types of transducers were considered: lead zirconate titanate ceramics and macrofiber composite devices. The experimental results indicate a clear relationship between the variation in the electrical impedance signature of the transducer and power spectral density obtained with the PLB method. Therefore, the PLB can be a simple and effective method for assessing the sensitivity of transducers for damage detection in SHM systems based on the EMI technique.