This study was carried out to evaluate the effect of natural ventilation and intermittent pumping events in hydrogen sulfide and methane dynamics, in terms of system operation and risk of gas exposure. Work was conducted in a full scale gravity sewer downstream of pumping stations, in Portugal. Different ventilation rates and locations were assessed, as well as H2S removal rates and potential exposure risk, through the opening of distinct manhole covers. Increased ventilation, resulting from opening of one manhole cover, saw a 38% increase in average pipe air velocity peaks, doubling the estimated rate of air turnovers per day, accompanied by an increase of nearly 20% in H2S average removal rate. Simultaneous opening of two manhole covers induced similar airflow rates through the vent stack, but different rates throughout the pipe. H2S removal rates were also found to differ, according to location of open manholes, but also initial H2S headspace concentration. Under more unfavourable conditions, natural ventilation did not suffice in attaining recommended safety concentrations, regardless of number and location of open manhole covers. H2S concentrations above defined thresholds were verified for all studied setups. Headspace oxygen concentrations below an 18.5% asphyxiation threshold also occasionally occurred, even at manholes immediately downstream of ventilation point.
The presence and fate of hydrogen sulfide in wastewater systems were studied in two stretches of an intercepting sewer system located in a coastal village, in Portugal. A range of hydraulic parameters were obtained and liquid and gas phase measurements were carried out, both continuously and through intensive sampling campaigns. Upstream, where flow rates were relatively low, dissolved sulfide concentrations around 12 mg S L−1 and hydrogen sulfide gas concentrations above 250 ppm were observed, along with limited corrosion damage. It is believed this is due to the low relative humidity detected along the atmosphere of the studied sewer system. Downstream, gas concentrations were always below 40 ppm. Despite that, high signs of corrosion were detected, particularly in manholes with drop structures. It is thought that condensation of spray produced by the fall is the main cause of the phenomenon. Another relevant observation was the rapid decline in dissolved sulfide contents along gravity trunk sewers following the discharge of rising mains, with loss rates as high as 40 mg S L−1 h−1. Air-flow velocities corresponded to 15–50% of wastewater flows, an observation which agrees with other authors9 publications addressing relatively small pipes and moderate water flows.
The work presented herein was carried out to assess the effect of intermittent pumping events in sewer headspace pressure differentials, as well as their relationship with hydrogen sulfide gas concentration. A full scale gravity sewer in Portugal, located downstream of several pumping stations, was used as the guiding case study. Under normal system operation, pressure difference between the outside atmosphere and the sewer headspace seemed to influence the in and out-gassing of gas pollutants emitted through the venting stack. Wastewater pumping cycles generated maximum pressure differentials of roughly 100 Pa, which in turn originated maximum air velocities of 1.76 m s−1 exiting the venting stack. Each pumping event was followed by a pressure drop of about 50 Pa, quickly attaining null concentrations of H2S at the venting stack. A statistically significant relationship between pressure differentials and air exit velocity was observed, which allowed obtaining an empirical equation for expedite prediction of airflows emitted to the outside atmosphere (R2 = 0.77). Conversely, the same effect was not observed along the length of the sewer pipe, unlike the findings of other studies. The effect of a full flowing pipe at the downstream end of the gravity trunk sewer was also noticeable in downstream sewer pressurization and gas build-up. It was concluded that the magnitude of the gas pollutant emissions may heavily depend on the impacts of hydraulic flows and pumping characteristics in headspace pressure differences, denoting the need for better approaches when designing and installing venting stacks.
For engineering purposes it is especially useful to be able to predict and control sewer corrosion rates and odor impacts as well as to design effective measures aiming to reduce effects related to hydrogen sulfide formation and release. Doing so, it is important to use modeling tools that are capable of assessing variations of dissolved oxygen, dissolved sulfide and hydrogen sulfide gas concentrations for a wide range of environmental scenarios. Two such models were assessed: AEROSEPT, an empirical formulation, and WATS, a conceptual and more complex approach. The models were applied to evaluate the effects of transitions between pressure mains and gravity sewers in the air–liquid mass transfer of hydrogen sulfide at the Ericeira sewer system in Portugal. This network is known to have odor and corrosion problems, especially during summer. Despite the unavoidable uncertainties due to the unsteady flow rate and the quantification of air velocity and turbulence, the simulation results obtained with both models have been shown to adequately predict the overall behavior of the system.
1 March 2018 in Journal of Environmental Management