Depending on the study of the master curve technique, a temperature correction model for the polarization current of transformer polymer (cellulose) insulation, considering the effects of both moisture content (mc%) and temperature is proposed. In the current work, the shift factors of polarization current curves of samples with various moisture contents are extracted at different temperatures. Then, the variation law among the shift factor, test temperature, and moisture content are studied so as to establish the corresponding functional relationship. The findings reveal that the modified model derived from the above functional relationship could be employed to perform the temperature correction of oil-immersed polymer samples with various insulation states. Therefore, the proposed temperature correction model in this paper will promote the state assessment of the field transformer polymer insulation.
The measurement of polarization and depolarization currents (PDC) based on time–domain response is an effective method for state assessment of cellulose insulation material in oil-immersed electrical equipment. However, the versatility of the data obtained at different temperatures is limited because of the temperature dependence of the PDC. In this respect, the universal conversion of PDC data at different temperatures is an essential aspect to improve the accuracy of the determination of insulating properties of cellulose materials immersed in the oil. Thus, an innovative temperature conversion method based on polarization time-varying current (PTC, obtained by multiplying the polarization current and time) is proposed in this article. In the current work, the PTC data at different temperatures are obtained from the oil-immersed cellulose pressboards with different moisture. Afterwards, the functional model based on the power series theory is used to simulate the PTC data, through which the coefficients of the power series are found related to the test temperature of the PTC and the moisture content (mc%) of the oil-immersed cellulose pressboards. Furthermore, the functional relationship among moisture, test temperatures, and the feature parameter calculated by these coefficients is established. Thus, the PTC data at various temperatures can be calculated by the established function. The potential application ability of the proposed method is verified by comparing the calculated results with the measured results obtained from the various samples.