Double Skin Façade (DSF) systems have become an alternative to the environmental and energy savings issues. DSF offers thermal buffer areas that can provide benefits to the conditioned spaces in the form of improved comforts and energy savings. There are many studies conducted to resolve issues about the heat captured inside DSF. Various window control strategies and algorithms were introduced to minimize the heat gain of DSF in summer. However, the thermal condition of the DSF causes a time lag between the response time of the Heating, Ventilation, and Air-Conditioning (HVAC) system and cooling loads of zones. This results in more cooling energy supply or sometimes less than required, making the conditioned zones either too cold or warm. It is necessary to operate the HVAC system in consideration of all conditions, i.e., DSF internal conditions and indoor environment, as well as proper DSF window controls. This paper proposes an optimal air supply control for a DSF office building located in a hot and humid climate. An Artificial Neural Network (ANN)-based control was developed and tested for its effectiveness. Results show a 10.5% cooling energy reduction from the DSF building compared to the non-DSF building with the same HVAC control. Additionally, 4.5% more savings were observed when using the ANN-based control.
This paper proposes the optimal algorithm for controlling the HVAC system in the target building. Previous studies have analyzed pre-selected algorithms without considering the unique data characteristics of the target building, such as location, climate conditions, and HVAC system type. To address this, we compare the accuracy of cooling load prediction using ANN and LSTM algorithms, widely used in building energy research, to determine the optimal algorithm for HVAC control in the target building. We develop a simulation model calibrated with actual data to ensure data reliability and compare the energy consumption of the existing HVAC control method and the two algorithms-based methods. Results show that the ANN algorithm, with a CV(RMSE) of 12.7%, has a higher prediction accuracy than the LSTM algorithm, CV(RMSE) of 17.3%, making it a more suitable algorithm for HVAC control. Furthermore, implementing the ANN-based approach results in a 3.2% cooling energy reduction from the optimal control of Air Handling Unit (AHU) Discharge Air Temperature (DAT) compared to the fixed DAT at 12.8 °C in a representative day. This study demonstrates that ML-based HVAC system control can effectively reduce cooling energy consumption in HVAC systems, providing an effective strategy for energy conservation and improved HVAC system efficiency.