Although amorphous alloy ribbons have lower core loss, serious loss deterioration occurs in amorphous cores constructed from amorphous alloy ribbon for distribution transformer. In the present study, the loss deterioration mechanism and influencing factors of amorphous cores for distribution transformers were investigated. The influence of distributed gaps on core loss of transformer core was calculated by simulation software and validated by experiments. The boron fluctuation of amorphous alloy ribbons affects the annealing temperature of amorphous transformer cores. A superior core annealing technique with annealing parameters was developed, and appreciable decrease in core loss was obtained.
The stress-impedance (SI) profiles were measured in ribbons annealed by Joule heating in the presence of longitudinal applied tensile stress of 100 MPa and the maximum SI ratio of 350% is observed. It was found that the large SI effect is the result of induced transverse magnetic anisotropy. We present a model that explains the variations of transverse magnetic anisotropy on SI effect. The model is based on the skin effect and on the magnetization rotation due to the applied tensile stress and the ac driving current.
1 October 2008 in Transactions of Nonferrous Metals Society of China