Passive Daytime Radiative Coolers (PDRCs) can cool buildings and cities by achieving subambient surface temperatures thanks to high solar reflectance and selectively high infrared emissivity within the atmospheric window. However, their performance is assessed outdoors with often too small samples and inconsistent experimental setups across the literature, which hinders intercomparison. Here, we demonstrate the limitations of current approaches and identify an experimental setup to achieve consistent and comparable results. We measured the surface temperatures of PDRC samples with different setups under both above-ambient and subambient conditions in temperate and desert climates, focusing on the effects of sample size and polyethylene (PE) film cover. Sample size introduced significant measurement uncertainty for air-exposed PDRC, resulting in overestimations of 1.2°C and 1.6°C under above-ambient and sub-ambient conditions, respectively. Further, PE film covers introduced greater deviations, up to + 3.0°C for above-ambient and − 2.7°C for subambient PDRCs. Instead, air-exposed PDRC samples of at least 200 mm, placed over insulation boards with reflectivity comparable to the PDRC, and with surrounding buffering boards, achieve a low measurement uncertainty of ± 0.3°C. Compared to this stable setup, other setups exhibit a large measurement bias, with 90% of this bias being systematic. Our findings underscore the need for consistent outdoor measurement methods to assess PDRC performance and enable quantitative analysis across the literature.