6 September 2024 in IEEE Transactions on Applied Superconductivity
Transformer winding subjected to alternating stresses caused by multiple short circuits can fail by fatigue even though the stress is below the yield point. The effect of the mean stress of unidirectional impulse pulsating short-circuit force is not considered in previous studies. Therefore, this paper proposes a general method for assessing the stress fatigue life and damage of transformer winding under short-circuit conditions. Take a 110 kV transformer for an instance, the electromagnetic forces and stresses on the winding under short-circuit conditions were calculated based on electromagnetic-structural coupling. The dynamic measurement of short circuit force is realized by using the piezoelectric thin film polyvinylidene fluoride (PVDF) sensor to verify the accuracy of the simulation calculation. Based on finite element stress results, this paper proposes a five-step method for calculating stress fatigue life, the S - N curve of the copper winding is estimated, and the short-circuit force of the unidirectional impulse is corrected under the consideration of the mean stress effect. Both the fatigue life and damage of transformer winding is analyzed using the Palmgren-Miner model. The proposed methodology can evaluate the number of stress cycles leading to transformer winding failure as well as the weak link of winding fatigue life.
3 October 2024 in IEEE Transactions on Applied Superconductivity
The considerable size and intricacy of high-power transformers frequently lead to inefficiency in finite element simulation analysis. To promptly and accurately estimate the stress state of the winding, this paper presents a theoretical approach to analyze the bending stress for each conductor in the inner winding of the transformer. Firstly, this approach takes into account the influences of conductor leakage flux and radial force as they vary with the radial position of the conductor. Subsequently, a 40000 kVA/110 kV transformer is adopted as a prototype, and the turn-to-turn winding model is constructed. The proposed analytical model is verified using 3D finite element method (FEM) simulations. Finally, a leakage flux test was conducted on the prototype, and the simulation and experimental results confirmed the validity of the proposed method.
22 July 2024 in IEEE Transactions on Applied Superconductivity
Whether the hot spot temperature rise exceeds the limit under long-term thermal effects and the impact of temperature rise effect on material parameters has attracted much attention. At the same time, as a key structural component of the transmission and transformation system, the calculation and verification of the winding mechanical strength of transformers during three-phase short circuits is a key factor in analyzing their stability during operation. Given that the previous analysis of the impact of transformer short-circuit strength only considered uniform temperature conditions, it is necessary to compare and analyze the impact of uneven temperature on winding stability. This article focuses on the SGB10-800 transformer prototype, conducting temperature rise experiments and simulation analysis to verify the accuracy of simulation processing. Conduct tests on the changes in force and deformation of wires under different temperature conditions. Finally, analysis of the impact of uneven temperature on the short-circuit strength of transformer windings.