15 March 2017 in IEEE Transactions on Power Systems
This paper proposes a generic pole-to-pole short-circuit fault current calculation method for dc grids. The calculation procedure begins from the simplified RLC equivalent model of a single modular multilevel converter, and then the prefault matrices and faulted matrices are established and modified to calculate the dc fault currents of all the branches. The proposed approaches are validated by comparing with the electromagnetic transient (EMT) simulation results on PSCAD/EMTDC. Besides, two case studies showed that the calculation method can be easily used to evaluate the severity of a dc fault. Moreover, the calculation can be applied to select the parameters of a fault current limiter (to match the circuit breaker capacity. The main contributions of the proposed numerical calculation method are: 1) The proposed method is accurate and much more time efficient than the EMT simulations; 2) the proposed method can handle all kinds of dc grid networks including the ring, radial, and meshed topologies; and 3) the proposed method is applicable to dc grid with multiple dc voltage level areas connected with dc/dc converters.
12 June 2015 in IEEE Transactions on Power Electronics
Modular multilevel converter (MMC) has become the most promising converter technology for high-voltage direct current (HVdc) transmission systems. MMC submodule (SM) topologies with dc fault ride-through capabilities are emerging which are suitable for overhead line applications. The hybrid SM design of each converter arm can get the compromise of higher capability of handling dc fault and lower capital investments and losses. In this paper, the initial hybrid SM numbers design method for supporting the dc-link voltage and riding-through dc faults and the optimized hybrid SM redundancy configuration strategy for effectively increasing the reliability of MMC are proposed and calculated. In contrast with the previously proposed redundancy configuration for MMC with the single SM topology, this approach solves the curvature of three-dimensional surface to calculate the recommended redundant hybrid SM numbers which takes both the semiconductor device utilization rate and the reliability of MMC into consideration.
10 July 2019 in IEEE Transactions on Power Delivery
This paper proposes a source-side DC fault current clearance scheme for HVDC grids under DC short-circuit faults. The scheme uses half-bridge sub-modules (HBSM) and full-bridge sub-modules (FBSMs) based hybrid MMC. The DC fault current behaviors of the HVDC grid is revealed as a primary criterion for the proposed approach. The additional degrees of freedom for control of hybrid MMC are incorporated into the HVDC grid to interrupt the fault current feeding at the source side. During the fault ride-through process, the reactive power compensation is maintained. The proposed method does not need the DC circuit breakers (DCCBs) since the current in the fault line can be controlled to zero. The primary and backup protection schemes for hybrid MMC-HVDC grid are proposed. The effectiveness of the method is validated by electromagnetic transient simulations on PSCAD/EMTDC.
23 August 2019 in IEEE Transactions on Power Delivery
Accurately determining the location of DC pole-to-pole short-circuit faults in modular multilevel converter (MMC) based multi-terminal HVDC (MTDC) systems is key issue in ensuring fast power recovery. This paper proposes an effective DC fault location scheme for the MMC-MTDC that uses an es-timated R-L representation of the transmission lines. By using the measured voltage and current data from both ends of the faulted DC line, the proposed fault location formulas can calcu-late the location of the fault with high accuracy. The simplified R-L representation greatly reduces the computation burden of the fault detection algorithm. Electromagnetic transient (EMT) simulations of a four-terminal MMC-MTDC system on PSCAD/EMTDC are used to confirm the effectiveness of the proposed approach. The paper also shows that the proposed scheme is robust and almost not affected by the transmitted power or the fault resistance.
1 May 2019 in IEEE Journal of Emerging and Selected Topics in Power Electronics
DC fault current limiters (FCL) are becoming increasingly important for the prompt DC fault clearance of modular multilevel converter (MMC) based HVDC grid. This paper proposes a hybrid FCL topology, in which the main current limiting circuit is composed of thyristors, capacitors and an inductor. Detailed theoretical analysis of the current limiting processes was carried out to check the electrical stresses. The relationship between the voltage stress and the current limiting time was analyzed, then a design method for the FCL parameters was provided. An effective method for fast bypassing the FCL inductor was proposed to reduce the energy dissipation when fault current is interrupted by a DC Circuit Breaker (DCCB). The dynamic performance of the proposed approach has shown that the proposed FCL can effectively limit the rate of rising of the DC fault current and reduce the energy dissipation.
20 December 2018 in IEEE Journal of Emerging and Selected Topics in Power Electronics
This paper introduces an enhanced DC fault current calculation method for modular multilevel converter (MMC) based HVDC grid. The new method considers the fast switching of the fault current limiters (FCL) and the nonlinear characteristics of the metal oxide arresters (MOA). The two peak-valley points of inflection in the DC fault current curves resulting from the insertion of the inductors and the energy dissipation in the MOAs, are discussed. The two points are selected as important indicators in the design of the coordinated protection scheme and switching logics. Then the impact of the total DC reactance distribution in the DC reactor and the FCL reactor, and the initial inductor current values on these two points are analyzed. Finally, the complete fault current calculation method including the action of DC circuit breakers (DCCB) is proposed. The method is validated by electromagnetic transient (EMT) simulations and has shown good applicability on both overhead line and cable based HVDC grids.