12 January 2022 in Energies
Verified
Journal Article
Open access
PDF file
GKGeniy Kuznetsov
Geniy Kuznetsov
NKNikolay Kopylov
Nikolay Kopylov
ESElena Sushkina
Elena Sushkina
AZAlena Zhdanova
Alena Zhdanova
Fire protection is a basic safety issue for all categories of buildings. The criteria for effective fire suppression and the characteristics of extinguishing systems in insulated areas depend on a combination of factors. The main influences include the type of combustible material, ambient temperature, type of spray extinguisher, air inflow and outflow conditions, and space geometry. This article analyzes the most widely used fire-extinguishing technologies in different locations. The main aspects of using the pulsed delivery technology of extinguishing liquid are considered. Based on the analysis of publications from the last decade, it is possible to develop intelligent systems for recording fires and extinguishing fires in the premises.

1 June 2019 in Vestnik Tomskogo Gosudarstvennogo Universiteta. Matematika i Mekhanika
Verified
Journal Article
Closed access
R(Russian Federation) Fgbu Vniipo Emercom Of Russia (Balashikha
Russian Federation) Fgbu Vniipo Emercom Of Russia (Balashikha
NKN.P. Kopylov
N.P. Kopylov
VKV.N. Karpov
V.N. Karpov
R(Russian Federation) Orenburg Branch Fgbu Vniipo Emercom Of Russia (Orenburg
Russian Federation) Orenburg Branch Fgbu Vniipo Emercom Of Russia (Orenburg
AKA.E. Kuznetsov
A.E. Kuznetsov
ESE.YU. Sushkina
E.YU. Sushkina

1 August 2020 in Occupational Safety in Industry
Verified
Journal Article
Closed access
FRFgbu Vniipo Of Emercom Of Russia
Fgbu Vniipo Of Emercom Of Russia
NKN.P. Kopylov
N.P. Kopylov
DFD.V. Fedotkin
D.V. Fedotkin
AKA.V. Karpov
A.V. Karpov
ESE.Yu. Sushkina
E.Yu. Sushkina
The decisive parameter in the design of automatic fire extinguishing systems in the depots for storing oil and oil products, the organization of fire extinguishing in the tanks with mobile equipment is the standard (critical) foaming agent supply rate. The purpose of this work is to evaluate the influence of the scale of model fire centers and their design on the values of critical intensity of the foam solution supply. The article presents the results of the analysis of the scientific studies of the process of oil products combustion and approaches to determining the standards for supplying a foaming agent solution to extinguish fires in the tanks. It is shown that the existing fire extinguishing modeling methods in the tanks do not fully take into account the effect on the extinguishing process of the following factors: the change in the rate of oil products burn-up depending on the tanks sizes, the transformation of the aerodynamic characteristics of the medium in the vicinity of the combustion zone, the scale and design of model combustion centers, means and methods of foam supply. The analysis of the work on estimating the burn-up rate of flammable liquids in the tanks of various diameters does not allow to conclude what the minimum size of the experimental tank should be, so that the results obtained for determining the critical intensity of the foam solution supply would not cause anyone doubts. The paper presents the results of mathematical modeling of changes in the heat flux density on the surface of burning gasoline in the tanks with a diameter of 3 m, 5 m and 21 m. It is shown that combustion in small-diameter tanks does not simulate the thermal regime of a fire implemented on the large-diameter tanks. Consequently, the foaming agent solutions critical on intensity supply for small and large tanks differ from each other. The combustion source used in a number of documents do not simulate the conditions for heating the side of a real tank, which explains the failure to extinguish fires in the large tanks. It is proposed to determine the intensity of the foaming solution supply, evaluate the efficiency of means and methods for producing foam in full-scale tanks or their mock-ups, which is economically justified and ensures the results reliability.

1 January 2022 in Vestnik Tomskogo Gosudarstvennogo Universiteta. Matematika i Mekhanika
Verified
Journal Article
Closed access
AFAll-Russian Research Institute of Fire Defense of the Ministry of Emergency Situations of the Russian Federation
All-Russian Research Institute of Fire Defense of the Ministry of Emergency Situations of the Russian Federation
NKNikolay P. Kopylov
Nikolay P. Kopylov
SKS. N. Kopylov
S. N. Kopylov
AKAleksey V. Karpov
Aleksey V. Karpov
DFDmitry V. Fedotkin
Dmitry V. Fedotkin
ESElena Yu. Sushkina
Elena Yu. Sushkina
Fundamental inefficiency of existing foam fire systems extinguishing tanks with oil and petroleum products having a volume of 5000 m3 or more is shown by methods of mathematical modeling. The required foam supply intensity and foam supply rate allowing effective fire suppression in large tanks with a volume of up to 20000 m3 are theoretically predicted. On this basis of theoretical conclusions, a new method of foam fire extinguishing in large fuel tanks has been developed. To obtain the required intensities and supply rates, fire extinguishing foam is formed in a special container with the use of solid-fuel gas generators. The theoretical predictions were confirmed in 21 full-scale successful experiments, in which fire suppresion system based on the new method was able to extinguish a fully developed gasoline fire in tanks with a volume of 5000 m3 and 20 000 m3 just for 30-90 seconds. The required amount of the foaming agent to extinguish a fire in a 20 000 m3 tank is only 450 liters, which is at least 100 times less than for traditional foam fire fighting Contribution of the authors: the authors contributed equally to this article. The authors declare no conflicts of interests.