Frequency control rebalances supply and demand while maintaining the network state within operational margins. It is implemented using fast ramping reserves that are expensive and wasteful, and which are expected to become increasingly necessary with the current acceleration of renewable penetration. The most promising solution to this problem is the use of demand response, i.e., load participation in frequency control. Yet it is still unclear how to efficiently integrate load participation without introducing instabilities and violating operational constraints. In this paper, we present a comprehensive load-side frequency control mechanism that can maintain the grid within operational constraints. In particular, our controllers can rebalance supply and demand after disturbances, restore the frequency to its nominal value, and preserve interarea power flows. Furthermore, our controllers are distributed (unlike the currently implemented frequency control), can allocate load updates optimally, and can maintain line flows within thermal limits. We prove that such a distributed load-side control is globally asymptotically stable and robust to unknown load parameters. We illustrate its effectiveness through simulations.
6 April 2018 in IEEE Transactions on Power Systems
This paper considers unbalanced multiphase distribution systems with generic topology and different load models, and extends the Z-bus iterative load-flow algorithm based on a fixed-point interpretation of the AC load-flow equations. Explicit conditions for existence and uniqueness of load-flow solutions are presented. These conditions also guarantee convergence of the load-flow algorithm to the unique solution. The proposed methodology is applicable to generic systems featuring i) wye connections; ii) ungrounded delta connections; iii) a combination of wye-connected and delta-connected sources/loads; and iv) a combination of line-to-line and line-to-grounded-neutral devices at the secondary of distribution transformers. Further, a sufficient condition for the nonsingularity of the load-flow Jacobian is proposed. Finally, linear load-flow models are derived, and their approximation accuracy is analyzed. Theoretical results are corroborated through experiments on IEEE test feeders.
7 August 2017 in IEEE Transactions on Power Systems
This paper examines distribution systems that have a high integration level of distributed energy resources (DERs), and addresses the design of local control methods for real-time voltage regulation. Particularly, the paper focuses on proportional control strategies wherein the active and reactive power output of DERs are adjusted in response to (and proportionally to) local changes in voltage levels. The design of the voltage-active power and voltage-reactive power characteristics leverages suitable linear approximations of the ac power flow equations and is network-cognizant; that is, the coefficients of the controllers embed information on the location of the DERs and forecasted noncontrollable loads/injections and, consequently, on the effect of DERs power adjustments on the overall voltage profile. A robust approach is pursued to cope with uncertainty in the forecasted noncontrollable loads/power injections. The stability of the proposed local controllers is analytically assessed and numerically corroborated.
12 January 2018 in IEEE Transactions on Control of Network Systems
This paper formalizes an optimal water-power flow (OWPF) problem to optimize the use of controllable assets across power and water systems while accounting for the couplings between the two infrastructures. Tanks and pumps are optimally managed to satisfy water demand while improving power grid operations; {for the power network, an AC optimal power flow formulation is augmented to accommodate the controllability of water pumps.} Unfortunately, the physics governing the operation of the two infrastructures and coupling constraints lead to a nonconvex (and, in fact, NP-hard) problem; however, after reformulating OWPF as a nonconvex, quadratically-constrained quadratic problem, a feasible point pursuit-successive convex approximation approach is used to identify feasible and optimal solutions. In addition, a distributed solver based on the alternating direction method of multipliers enables water and power operators to pursue individual objectives while respecting the couplings between the two networks. The merits of the proposed approach are demonstrated for the case of a distribution feeder coupled with a municipal water distribution network.
25 January 2018 in IEEE Transactions on Power Systems
This paper develops an approach to enable the optimal participation of distributed energy resources (DERs) in inertial- and primary-frequency response alongside conventional synchronous generators. Leveraging a reduced-order model description of frequency dynamics, DERs' synthetic inertias and droop coefficients are designed to meet time-domain performance objectives of frequency overshoot and steady-state regulation. Furthermore, an optimization-based method centered around classical economic dispatch is developed to ensure that DERs share the power injections for inertial- and primary-frequency response in proportion to their power ratings. Simulations for a modified New England test-case system composed of ten synchronous generators and six instances of the IEEE 37-node test feeder with frequency-responsive DERs validate the design strategy.
3 December 2018 in IEEE Transactions on Automatic Control
Frequency restoration in power systems is conven- tionally performed by broadcasting a centralized signal to local controllers. As a result of the energy transition, technological advances, and the scientific interest in distributed control and optimization methods, a plethora of distributed frequency control strategies have been proposed recently that rely on communication amongst local controllers. In this paper we propose a fully decentralized leaky integral controller for frequency restoration that is derived from a classic lag element. We study steady-state, asymptotic optimality, nominal stability, input-to-state stability, noise rejection, transient performance, and robustness properties of this controller in closed loop with a nonlinear and multivariable power system model. We demonstrate that the leaky integral controller can strike an acceptable trade-off between performance and robustness as well as between asymptotic disturbance rejection and transient convergence rate by tuning its DC gain and time constant. We compare our findings to conventional decentralized integral control and distributed- averaging-based integral control in theory and simulations.