In order to address the convergence issue in fuzzy power flow calculations, this paper proposes an analytical approach based on the Levenberg–Marquardt method, aiming to improve the convergence of the fuzzy Newton power flow method. Firstly, a detailed analysis is conducted on the convergence theorem and convergence behavior of the fuzzy Newton method, revealing its poor convergence when the initial values are not properly selected. The Levenberg–Marquardt method is then selected as a means to enhance the convergence of the fuzzy Newton power flow calculations, specifically to tackle the problem of initial value deviation. Since the Jacobian matrix has a significant impact on the convergence region of the power flow, this paper reconstructs the Jacobian matrix based on the Levenberg–Marquardt method, effectively enlarging the convergence region. Through validation experiments on the IEEE 118 standard nodes and simulation comparative analysis, the results confirm the method’s effectiveness in resolving the problem of initial value deviation and notably enlarging the convergence region, thereby improving the convergence of power flow calculations.
With the increasing scale of cross-basin hydraulic engineering and cascaded hydropower stations, hydraulic systems exhibit complex characteristics such as long-distance, nonlinear, and multivariable coupling. The dynamic interaction among hydraulic parameters can easily induce pressure oscillations and flow fluctuations, posing a serious challenge to the safe and stable operation of the system. To address the control problem caused by the impact of hydraulic coupling on the output of complex hydraulic systems, this paper proposes a synergetic feedforward control method based on the rate of water level change in the surge tank. This method uses the rate of water level variation as a real-time indicator of hydraulic coupling intensity and, through theoretical derivation, establishes an analytical relationship between the guide vane opening compensation and the rate of water level change for each unit. For complex topological configurations, the feedforward weight coefficients are separately derived for single penstock–single machine systems and single penstock–two machine systems. Theoretical analysis shows that the proposed method automatically resets to zero under steady-state conditions, fundamentally eliminating the issue of steady-state opening deviation. It also exhibits phase-leading characteristics, enabling it to act in advance during the early stage of a disturbance. In addition, filtering is applied to suppress wave spikes that occur under certain parameter settings. Simulink simulations have verified the effectiveness of this method in mitigating hydraulic coupling, and the influence of key parameters on control performance has also been analyzed.