11 July 2025 in IEEE Transactions on Industrial Electronics
Since that time delay is dominant in most industrial systems, it can reduce the stability and control performance of the closed-loop system. This article proposes a delay-inertia-compensation active disturbance rejection control (DIC-ADRC) for time-delay dominant industrial systems, where these systems can be approximated as second-order plus time-delay (SOPTD) systems. Different from a regular pure-delay compensation part, a compensation part combined with a pure-delay and first-order inertia is added to the control signal before it is sent to the extended state observer, where the SOPTD system can be approximated as a combination of a low-frequency integrator and a pure-delay. Quantitative tuning rules are derived to facilitate the application of DIC-ADRC, allowing controller parameters to be computed from the model and adjusted as needed. A stability theorem is also proposed and rigorously proven, ensuring closed-loop stability when its conditions are met. Comparative simulations and dual-tank experiments demonstrate that the proposed control method exhibits strong robustness and satisfactory control performance, while also validating the effectiveness of the DIC-ADRC quantitative tuning rules. Finally, further validation of DIC-ADRC is conducted through field application on the main steam pressure process. Compared to the original controller, DIC-ADRC demonstrated superior control performance. The results from both simulations and experiments reveal that DIC-ADRC has excellent control performance on time-delay systems and can be widely used in real industrial systems.