1 January 2019 in Mathematical Problems in Engineering
In order to handle heavy chattering and negative robustness caused by time‐varying system parameters and external load disturbance of the speed control system, thereby having high‐precision control over surface permanent magnetic synchronous machine (PMSM), this paper combines the advantages of sliding mode variable structure control (SMVSC) and fuzzy control. Firstly, a fuzzy sliding mode variable structure control (FUZZY‐SMVSC) method is proposed, based on the vector control foundation framework of surface PMSM (SPMSM). It effectively reduces chattering while keeping sliding mode, according to the fuzzy rules formulated based on fuzzy control principle. Secondly, integral sliding mode surface is used and integration element is introduced into fuzzy control input, thereby reducing the static error of the conventional fuzzy control. Simulation and experimental results show that the proposed fuzzy sliding mode variable structure control reduces chattering by fuzzy reasoning and softening. Also, it still can maintain the strong robustness of sliding mode variable structure and ensures the fine dynamics of the system, against time‐varying system parameters and external load disturbance.
27 December 2018 in Journal of Control Science and Engineering
Chilled water system of central air conditioning is a typical hybrid system; variable frequency behavior with amplitude limited of pumps reflects continuous and discrete dynamic characteristics. The way of energy-saving is variable water volume, via variable frequency behavior of pumps to gain adjustment of power consumption. Facing the situation of the variable frequency pumps with parallel operation, single continuous or discrete modeling cannot reflect the hybrid features. Thus, the control method will have some questions, such as bad energy-saving effect, difficult accurate adjustment of cold capacity, and low running energy efficiency. However, hybrid system modeling can reflect hybrid dynamic behavior of pumps, which is combining continuous and discrete features. The questions of nonlinear and multiparameters can be solved by control method based on hybrid system. Here, an optimum control method is proposed with the principle of the minimum, by setting the minimum power consumption as the performance function in fixed time, which realizes variable control of pumps and accurate adjustment of temperature inside room. At last, it shows the system characteristics and energy-saving affection by hybrid system modeling and the optimum control method.
8 July 2018 in Mathematical Problems in Engineering
Currently in China, energy conservation and emission reduction are important initiatives for society. Because of its large proportion of building energy consumption, several methods for building energy conservation have been introduced for central air conditioning. This paper presents a hybrid system for a modelling and control approach. By analysing the cooling capacity transfer process and the electromagnetic properties of pumps, the modelling is performed in a hybrid system framework. Pumps are classified as fixed-frequency pumps, variable-frequency pumps, and switchable pumps; a switch control strategy is used in the chilled water system for supplying cooling capacity. In order to adjust indoor temperature and save electrical energy, the cooling capacity allocation and average temperature methods are presented, which satisfy the goal of optimal control of real-time energy consumption. As a numerical example, the temperature variation and cold regulation processes are simulated. Three rooms are the control objects that lower the setting points, and pumps waste as little electrical energy as possible. The results show 49.4% of water pump power consumption when compared with constant water volume technology. The modelling and control approach is more advantageous in ensuring the success of reconstruction projects for central air conditioning.
1 January 2019 in Mathematical Problems in Engineering
The chilled water system of central air conditioning is a typical hybrid system. The dynamic adjustment of cooling capacity based on hybrid system can achieve accurate temperature control and real‐time energy saving. Mixed logical dynamical (MLD) systems have advantage for solving constrained optimization problems of this type of case by numerical methods. This paper proposes a novel modified type of MLD system, which enhances the model applicability and improves the switching flexibility and control effect for the framework. In order to meet the needs of cooling capacity and energy saving, the optimal control problem is transformed as MIQP problem by defined performance index. As a numeral example of application, the model and control method is used in pumps group control for variable water volume in chilled water system of central air conditioning. At last, the dynamic and energy‐saving effects of the system are simulated, which shows the ideal control results.
8 August 2018 in Mathematical Problems in Engineering
This paper proposes a new type of multiswitching system and a subsystems-group as a basic switching unit that obeys the law. Unlike traditional switching systems, the system selects multiple subsystems instead of one on each time interval. Thus, a framework of parallel structure organizes the subsystems as a group. A multiswitched system is widely used in engineering for modelling and control; this system reflects the actual industrial dynamical process. Thus, the stability of the system is studied. Assuming that these continuous and discrete-time subsystems are Hurwitz and Schur stable, the subsystems-groups matrices commute each other based on the subsystems matrices pairwise commutative. Then, the multiswitched system is exponentially stable under arbitrary switching, and there exists a common Lyapunov function for these subsystems. The main result is extended to a parallel-like structure; therefore, some stability results are gained under some reasonable assumption. At last, a numeral example is given to illustrate the structure and the stability of this system.