23 August 2010 in IEEE Transactions on Power Delivery
In this paper, a novel method for fault classification in single-circuit transmission lines is presented. The proposed method needs voltages and currents of only one side of the protected line. After detecting the exact time of fault inception, the fault type is recognized by means of a decision-tree algorithm (DT) which is formerly trained by applying the odd harmonics of the measured signals, up to the 19th. Simulation results have shown that the proposed method can classify the faults in less than a quarter of a cycle with highest possible accuracy.
10 May 2011 in IET Generation, Transmission & Distribution
In this study a new pattern recognition-based algorithm is presented for detecting high impedance faults (HIFs) in distribution networks with broken or unbroken conductors and distinguishing them from other similar phenomena such as capacitor bank switching, load switching, no-load transformer switching (through feeder switching), fault on adjacent feeders, insulator leakage current (ILC) and harmonic load. The proposed method has employed multi-resolution morphological gradient (MMG) for extraction of the time-based features from three half cycles of the post-disturbance current waveform. Then, according to these features, three multi-layer perceptron neural networks are trained. Finally, the outputs of these classifiers are combined using the average method. Applying the data for HIF, ILC and harmonic load from field tests and for other similar phenomena from simulations has shown high security and dependability of the proposed method. Also, a comparison between the features from the proposed MMG-based procedure and the features from discrete Fourier transform, discrete S-transform, discrete TT-transform and discrete wavelet transform is made in the feature space.
10 April 2014 in IEEE Transactions on Dielectrics and Electrical Insulation
MAMohsen Bakhshi Ashtiani
Noise reduction is one of the important tasks of partial discharge (PD) detection and investigations in the process of cable insulation assessment. Singular Value Decomposition (SVD) is an algorithm, which can be employed in noise reduction from partial discharge signals, based on separation of singular values corresponding to noise and PD signal. In this paper, a new idea is presented providing generalization and practicality of the method in selection of singular values for detection and/or reconstruction of de-noised PD pulses. This procedure named as Adaptive Singular Value Decomposition (ASVD) has been examined on field measured, laboratory recorded and simulated signals and its results have been compared with the results of some published methods. The proposed method cleans up polluted PD pulses, even in excessive noisy conditions, resulting in higher signal-to-noise ratios (SNRs) rather than the results of other mentioned methods. Comparing in terms of magnitude, falltime, and pulse-area of PD signals after de-noising, the proposed method also preserves the features of PD pulses from distortions and errors much better than the compared methods.
14 June 2013 in IEEE Transactions on Power Delivery
In this paper, a novel method for fault location in multiterminal transmission lines is presented. The method is based on applying the S-transform to the modal components of synchronized measured currents at different terminals to extract time of arrival of the first arrived transient wave generated by the fault. These arrival times are then reported to a central processor where they are converted to distance indices and involved in a decision procedure. The simulation results have shown good performance of the proposed method under different fault resistances, fault inception angles, fault locations (even on tap points), fault types, and faulted sections.
27 November 2012 in IEEE Transactions on Power Delivery
In this paper, for the first time, a high-impedance fault indicator (HIFI), to be mounted on the poles of distribution feeders, is proposed to detect and track down the location of high-impedance faults (HIFs). The main contribution of this paper is the investigation of employing the magnetic-field strength signal, measured in the vicinity of the conductors of a feeder, to detect HIFs based on a novel pattern recognition method. The proposed HIFIs should be installed so that the faulted branch identification becomes possible and simple (i.e., at the sending ends of branches). Applying the data for HIFs, insulator leakage current and harmonic load from field tests and for other similar phenomena from simulations has shown high security and dependability of the proposed method as a computational model for HIFI.
15 October 2018 in IEEE Transactions on Power Delivery
Locating high impedance fault (HIF) in a distribution network enhances the reliability of the system and improves the quality of the service for the customers. Due to low magnitudes of fault current and nonlinearity of fault impedance it is a very hard task and less considered by the distribution automation system. This paper introduces a novel method for estimating the location of high impedance arcing faults in radial distribution systems. The proposed method searches the feeders of the network at different locations, to find where the estimated parameters of the assumed HIF would result the most accurate estimation of the faulty phase voltage. The fault current and the arc parameters are estimated at each probable location employing an appropriate model to estimate the faulty phase voltage. As the proposed method uses the time domain analysis, it is applicable for nonhomogeneous distribution networks with unbalanced loading as well as symmetrical systems. The results of simulations of IEEE 34-node test feeder with various HIF parameters by EMTP-RV show that the proposed method is well capable of locating high impedance faults despite uncertainty in the load data.