9 July 2024 in IEEE Transactions on Instrumentation and Measurement
To detect partial discharge (PD) signals generated by poleymer insulation in power equipment, the generation and propagation characteristics of PD vibration signals are studied in polymer materials. Firstly, the generation and propagation of PD vibration signals in polymer insulation are described as a second-order model. Then, based on the theoretical analysis, dynamic mechanical analysis and acoustic propagation experiments reveals that polymers with higher Young’s modulus exhibit lower initial amplitude of vibration signal generated by partial discharge (PD). Meanwhile, Polymers with higher viscous damping not only display smaller initial vibration amplitudes and greater propagation attenuation, but also demonstrate shorter signal durations. Furthermore, the phenomenon is found and certificated that crystallization plays a crucial role in vibration propogation in poleymer materials. Increased crystallinity will lead to increase viscous damping coefficient of poleymers. Finally, Erbium and ytterbium co-doped π Phase Shifted Grating (EYDF-π-PSG) laser was used to measure PD vibration signals. Vibration signals detection experiments are finished in crosslinked polyethylene (XLPE) and methylsilicone rubber (MQ), seperately. Compared to XLPE material with higher modulus value and viscous damping coefficient, the PD viberation signals are easily detected in MQ material.
5 September 2025 in IEEE Sensors Journal
Insulation failure is one of the most significant threats to the safety of cable joints. Partial discharge (PD) detection is the most effective method to recognize potential faults in polymer insulation of cable joints. Distributed feedback fiber laser (DFB-FL) acoustic sensing proves highly effective in monitoring partial discharges ultrasonic for liquid insulation. However, the acoustic attenuation in cross-linked polyethylene (XLPE) insulation materials employed for cable joints limits PD ultrasonic propagation to a mere 7-10 cm range. The single point DFB-FL sensing unit is inadequate for detecting PD acoustic signals across mete-length XLPE material of cable joints due to its limited spatial coverage. This paper proposes a novel collaborative sensing method with DFB-FL and Fiber Bragg Grating (FBG), which expands the single point measurement to multiplexing measurement and constructs a dense sensor array to monitor partial discharge signals within cable joint insulation. Meanwhile, a synchronized center wavelength tuning method is presented to compensate for the working-point drift caused by temperature rise during cable joint operation. Then, the DFB-FL/FBG collaborative sensing system is used to detect partial discharge acoustic signals in 110kV XLPE cable insulations. The experiment results demonstrate that DFB-FL/FBG collaborative sensing system can detect acoustic signals generated from PD at 70cm range at 200-300 pC apparent charge. Finally, based on the comparative analysis of different FBG topological structures, the evidence suggests that the serial FBG network structure will reduce signal-to-noise ratio and sensitivity, but parallel-arrayed FBG structure minimally impacts these parameters when combining DFB-FL with multiple FBGs. The hybrid structure combines advantages of both series and parallel structure, enabling larger-area polymer insulation partial discharge acoustic measurement at lower cost.