Shipu Wu

Shipu Wu

Auto-generated profile, based on publicly available information

Shipu Wu

1) State Key Laboratory of Reliability and Intelligence of Electrical Equipment Hebei University of Technology, Tianjin, 300130, China 2) Key Laboratory of Electromagnetic Field and Electrical Apparatus Reliability of Hebei Province Hebei University of Technology, Tianjin, 300130, China

Research Focus & Metrics

Academic Career Length

7Years (2020-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
21 May 2021 in IEEE Transactions on Magnetics
Verified
Journal Article
Closed access
SWShipu Wu
Shipu Wu
YRYuzhan Ren
Yuzhan Ren
YWYouhua Wang
Youhua Wang
CHCailing Huo
Cailing Huo
CLChengcheng Liu
Chengcheng Liu
Power transformer is the main part of the power grid. After some tests and operations of transformers, a certain residual flux density ( $B_{r}$ ) is left in the iron core due to the ferromagnetic material hysteresis phenomenon. When the transformer is switched on with no load, $B_{r}$ will lead to inrush current. Therefore, research on measuring $B_{r}$ is of great significance for transformer protection. In this article, a $B_{r}$ measurement method based on applied dc voltage is proposed. First, combined with the magnetic circuit and transient circuit analysis, the relationship between $B_{r}$ and the extremum value of the transient current difference is obtained. Then, the finite element method (FEM) is used to calculate the transient current under different $B_{r}$ and test circuit parameters; the suitable test circuit parameters will be determined, and then the empirical formula for calculating $B_{r}$ is obtained. Finally, the experimental results verify the correctness of the simulation analysis.

1 January 2021 in AIP Advances
Verified
Journal Article
Open access
PDF file
YYYiming Yang
Yiming Yang
YWYouhua Wang
Youhua Wang
SWShipu Wu
Shipu Wu
CLChengcheng Liu
Chengcheng Liu
LCLong Chen
Long Chen
Soft magnetic composite (SMC) is composed of ferromagnetic particles surrounded by electrical insulation layer. During the manufacturing process, the electric insulation layer may be destroyed and thus the eddy current will be induced, which makes it difficult to calculate the accurate eddy current loss. In this paper, the inter-particle eddy current loss is calculated at the macro-scale by modeling the actual sample and using the measured conductivity of the sample, moreover intra-particle eddy current loss is calculated by modeling single particle of SMC base on the existing model. Then, under different particle sizes and frequencies, the influence of skin effect on the calculation of eddy current loss is analyzed. Finally, to verify the proposed model, the iron losses of two SMC materials are calculated and they are compared with measured results. It can be seen that when the inter-particle eddy current loss has been considered, then the core loss of SMC will be agreed very well with the measurement results, thus the proposed model can be used for the actual core loss calculation for the electrical machine or other electromagnetic device with SMC cores.

19 June 2020 in IEEE Transactions on Magnetics
Verified
Journal Article
Closed access
CHCailing Huo
Cailing Huo
YWYouhua Wang
Youhua Wang
SWShipu Wu
Shipu Wu
YYYiming Yang
Yiming Yang
ZZZiwei Zhao
Ziwei Zhao
The residual flux measurement is one of the difficulties in the transformer research field. This paper presents a residual flux density (Br) measurement method considering the relative differential permeability (μrd) of the core material. Firstly, the basic relationship between μrd and Br is analyzed on the basis of the magnetic domain theory. Then, combining the experimentally measured relationship between Br and μrd, using μrd as an intermediate variable, the relationship between Br and time constant is derived. Furthermore, a square iron core model is established by the finite element method, and the empirical formula for calculating Br is fitted. Finally, the feasibility of this method and the accuracy of the proposed empirical formula are verified through experiments.

3 November 2021 in IEEE Transactions on Instrumentation and Measurement
Verified
Journal Article
Closed access
CHCailing Huo
Cailing Huo
YWYouhua Wang
Youhua Wang
SWShipu Wu
Shipu Wu
CLChengcheng Liu
Chengcheng Liu
When the power transformer is reconnected to the power grid, and if there is a large residual flux in the iron core, an inrush current may result. To suppress inrush current, the detailed information of the residual flux needs to be known. In this article, a residual flux density measurement method for a single-phase transformer core based on energy changes is proposed. First, when positive and negative dc voltages (referred to as the direction along or opposite to the initial residual flux density) are applied, the positive and negative energy changes of the power source can be obtained by measured response currents. Then, the direction of the residual flux density is determined by comparing the gained energy changes. The magnitude of residual flux density can be calculated by the empirical formula between residual flux density and positive energy. The square iron core is investigated in this work to establish the corresponding empirical formula by finite element method. Finally, the accuracy of the empirical formula is verified on the experimental platform. The results show that the relative error of the proposed method is within 5%, which has higher accuracy than existing methods.

1 February 2023 in AIP Advances
Verified
Journal Article
Open access
PDF file
YRYuzhan Ren
Yuzhan Ren
YWYouhua Wang
Youhua Wang
CLChengcheng Liu
Chengcheng Liu
SWShipu Wu
Shipu Wu
A serious inrush current may occur when a power transformer is re-energized, which will cause many adverse effects on power equipment and the power grid. The corresponding potential hazards can be reduced if the existing residual flux density (Br) can be accurately measured. Combined with the field-circuit coupling analysis method, a novel method for measuring the Br based on the phase difference between the applied AC voltage and resulting transient current is proposed in this paper. When the same AC voltage is applied to the transformer winding, the Br affects the resulting transient current. The phase difference between the applied voltage and the resulting current can be calculated by the cross-correlation technique. Based on the finite element method (FEM), the empirical formula for the quantitative measurement of Br in the transformer core is determined. Finally, an experimental study is performed on the square core of single-phase transformers. The experimental results reveal that the proposed measurement method is with high accuracy.