This article proposes a novel inertia emulation and fast frequency-droop (IEFF) control strategy for a point-to-point voltage source converter-based high voltage direct current (VSC-HVdc) transmission system. It allows asynchronous ac grid synchronization in forms of inertial and fast frequency-droop responses provided to “both” sides of the VSC-HVdc interconnected grids, different from the historically reported schemes only providing these responses to one grid. Under the IEFF scheme, the power-regulating VSC (PR-VSC) station emulates a synchronous generator directly through its active power control, whereas the dc-voltage-regulating VSC (DR-VSC) station employs a dc voltage/frequency droop control to convey its connected grid frequency communication-free to the remote PR-VSC for inertial and fast frequency-droop oriented power variations. To avoid the clash of the PR-VSC IEFF and DR-VSC IEFF control under simultaneous frequency events in the asynchronous grids, a novel frequency support mode selection scheme is designed to effectively prioritize the IEFF support with a higher frequency gradient. The key parameters of the IEFF controller are optimized through small signal stability analysis. The effectiveness of the proposed IEFF scheme is verified through controller hardware-in-the-loop experiments. The results show that the proposed IEFF scheme effectively promotes synchronization and enhances overall frequency stability for the two interconnected asynchronous grids.
Hybrid HVDC system, which comprises a line commutated converter (LCC) at rectifier side and a voltage source converter (VSC) at inverter side, is drawing wide attention due to its high reliability and economic benefit. For such a new transmission technology, the system characteristics are not comprehensively studied, and inappropriate control parameters may be coherent to system instability. This paper puts forward a novel coherence analysis procedure which analyzes system stability based on a verified hybrid HVDC small-signal model. For the first time, the procedure is proposed to capture the coherence relationships between the system characteristics and control parameters. The analysis results reveal: the circuit and control parameters can highly affect the oscillatory modes and even cause instability. Moreover, the variation of grid Short Circuit Ratio (SCR) at LCC rectifier side trades off the response speed and damping of the oscillatory modes - under low SCR, large proportional and small integral coefficients of the LCC DC current control are suggested to enhance response performance. Also, the increase of VSC DC capacitance reduces the mode response speed - for a large capacitance, large proportional and small integral coefficients of the VSC DC voltage control shall be set to guarantee system stability.